CAUTION   DO NOT install it in the following places.

1. Places exposed to direct sunlight
3. Places near heat devices
5. High humidity places

    Detach the back lid.
    Insert the batteries. (two AAA batteries)
    Reattach the back lid.

Wood screw

Holder for

remote controller

Ensure the correct 

polarity when

inserting.

In case of plural setting, check the operation distance of wireless remote controller, and avoid mixed
communication.
Refer to

7 Wireless remote controller unit operation distance

  on page 364 about the operation distance.

It is necessary to change setting of interface PCB and wireless remote controller.
(1) Interface PCB 

Set SW1-1 to “OFF” position.

(2) Wireless remote controller

Pressing ACL  and  AIR FLOW button at the same time or inserting the batteries with 
pressing  AIR FLOW button will customize the signal.

VRF system (except heat recovery 3-pipe system) cannot be operated in Auto mode.
Make sure to set the remote controller for the models so as not to be able to choose 
Auto mode.
Pressing ACL  and  MODE button at the same time or inserting the batteries with 
pressing  MODE button will make auto mode operation.

ATTENTION

When the batteries are removed, the setting will return to the default setting. Please 
make sure to reset it when the batteries are replaced.

     Caution

Instruct the customer to set the mentioned above when replacing the batteries.
(How to set is also mentioned in the user’s manual attached on the air conditioner.)

Auto mode operation setting

Radio prevention mode

2. Hot surface or cold surface enough to generate condensation
4. Places directly exposed to oil mist or steam
6. Uneven surface

Installation tips for the remote controller holder

How to insert batteries

Setting to avoid mixed communication

Setting to disable the Auto mode operation

Up to two wireless kit or wired remote controller can be installed in one indoor unit group.
When two wireless kit or wired remote controller are used, it is necessary to change setting on the PCB to slave.

Master/Slave setting when using plural remote controllers

Switch

Setting
Master

Slave

Contents

Master remote controller

Slave remote controller

Wired remote controller: SW1
Wireless kit: SW1-2

Function setting of interface PCB and wireless remote controller

5

• Adjust and keep the holder up right.
• Tighten the screw to the end to avoid scratching the remote controller.
• DO NOT attach the holder on plaster wall.

How to install the wireless remote controller

4

1
2
3

5

8

6

Trial operation

8

The backup switch is provided on the receiver section. It is possible to use the backup switch as shown in the 
figure below. When operation from the wireless remote controller unit is not possible (due to flat batteries, a 
mislaid unit, a unit failure), the backup switch can be used as an emergency means. The backup switch is 
operated manually.
(1) If pressed while the air conditioner is in a halt, it will cause the air conditioner to start operation in the 

automatic mode (in the case of cooling only, in the cooling mode).
Fan speed: Hi fan, Temperature setting: 23

o

C, Louver: horizontal

(2) If pressed while the air conditioner is in operation, it will stop the air conditioner.

• After safety confirmation, turn on the power.
• Transmit a cooling operation command with the wireless remote controller, while the backup switch on the 

receiver is depressed.

• If the backup switch on the receiver is pressed during a test run, it will end the test run.
• If the air conditioner can not operate properly during the test run, check wiring according to the trouble shooting 

guides.

Backup switch

Cooling test run operation

Backup switch

<

FDK71

>

<

FDK22-56

>

7

Backup switch

NOTE

1. After over 2 minute from power on, operate the wireless remote controller.

The operation is invalid during 2 minute from power on.

2. Check indicator lamp “check1” / “check2” shows error code.

The number of blinking shows the error code number of tens/ones place and check1/check2 corresponds to 
tens/ones place.

Wiring

6

Wireless remote controller operation distance

7

Up to 16 indoor units can be connected.

    Connect indoor units with each other with 2-core wires. As 

for size, refer to the following note.

The receiver wires must be connected only with the indoor 

unit that will be operated by the remote controller directly.

    Use the rotary SW1 and SW2 provided on the indoor unit 

PCB (Printed circuit board) to set unique remote control 
communication address avoiding duplication.

Points for attention in connecting a plural number of indoor units

[Condition]

Illuminance at the receiver area: 360 lux.

Control plural indoor units with one remote controller

Restrictions on the thickness and length of wire 
(Maximum total extension 600m.)

Standard Within 100m x 0.3mm

2

Within 200m x 0.5mm

2

Within 300m x 0.75mm

2

Within 400m x 1.25mm

2

Within 600m x 2.0mm

2

1

2

3

1

2

60

o

60

o

(Top view)

5m

5m

Receivable range

Receivable range

5m

    Standard signal receiving range

[Condition]

Illuminance at the receiver area: 360 lux.
(When no lighting fixture is located within 1m of indoor unit in an ordinary office)

60

o

5m

Receivable range

(Top view)

Outdoor unit

No.01

Indoor unit
Outdoor No.01
Indoor    No.01

Indoor unit
Outdoor No.01
Indoor    No.02

Indoor unit
Outdoor No.02
Indoor    No.04

Indoor unit
Outdoor No.02
Indoor    No.05

Indoor unit
Outdoor No.02
Indoor    No.06

Indoor unit
Outdoor No.01
Indoor    No.03

Outdoor unit

No.02

Interface PCB

Receiver

8

Remote controller line
(No polarity)

1m

2.0m

Floor surface

Within 5m

Wireless remote

controller unit

Содержание RCN-K-E

Страница 1: ...ed to oil mist or steam directly 6 Uneven surface 7 Places affected by the direct airflow of the AC unit 8 Places where the receiver is influenced by the fluorescent lamp especially inverter type or sunlight 9 Places where the receiver is affected by infrared rays of any other communication devices 10 Places where some object may obstruct the communication with the remote controller DO NOT leave t...

Страница 2: ...to operate it correctly referring to the instruction manual For the installation method of the air conditioner itself refer to the installation manual enclosed in the package DO NOT install it on the following places PHA012D038 Attention 1 Places exposed to direct sunlight 2 Places near heat devices 3 High humidity places 4 Hot surface or cold surface enough to generate condensation 5 Places expos...

Страница 3: ...e attached wiring assy B c Bundle wiring with attached ties d Install the interface PCB assy on the left cover of the indoor unit with the attached insulation Refer to below figure 1 In case of the piping routed from right side Put back Panel and stick Label on Panel Refer to 3 How to install the control assy Put back Panel and stick Label on page 362 Fixing base Fixing base Fix with insulation Fi...

Страница 4: ... the left FDK22 56 FDK71 Fix with insulation Fix with insulation Fixing base Fixing base Fix Wiring assy for X Y a Fix the terminal of the wiring assy for X Y on the terminal block of the indoor unit Non polarized b Route the wiring as shown in figure c Bundle wirings with attached ties 5 Install interface PCB assy on Indoor unit a Install the cover in which the interface PCB assy is installed 4 P...

Страница 5: ...nit bottom lid and fasten the fixing screw A only FDK22 56 1 Stick Label on Panel Stick the attached label on the front panel Label must be stuck under the left side LED of the front panel Label must be stuck under the right side LED of the front panel 2 1 2 1 2 Label and have 2 dots Matched the dot on the label and the bottom of the LED hole FDK22 56 FDK71 Label 1 Label 2 Put back Panel and stick...

Страница 6: ...When the batteries are removed the setting will return to the default setting Please make sure to reset it when the batteries are replaced Caution Instruct the customer to set the mentioned above when replacing the batteries How to set is also mentioned in the user s manual attached on the air conditioner Auto mode operation setting Radio prevention mode 2 Hot surface or cold surface enough to gen...

Страница 7: ...tions on the thickness and length of wire Maximum total extension 600m Standard Within 100m x 0 3mm2 Within 200m x 0 5mm2 Within 300m x 0 75mm2 Within 400m x 1 25mm2 Within 600m x 2 0mm2 1 2 3 1 2 60o 60o Top view 5m 5m Receivable range Receivable range 5m Standard signal receiving range Condition Illuminance at the receiver area 360 lux When no lighting fixture is located within 1m of indoor unit...

Страница 8: ...ioner is in operation it will stop the air conditioner After safety confirmation turn on the power Transmit a cooling operation command with the wireless remote controller while the backup switch on the receiver is depressed If the backup switch on the receiver is pressed during a test run it will end the test run If the air conditioner can not operate properly during the test run check wiring acc...

Страница 9: ...RC E3 Unit mm PHA001Z022 ...

Отзывы: