Eng-32
Airflow
Adjust the output of the fan speed.
Note
• Each fan speed can set from 25% to 100% of output by 5% pitches.
• The supply fan speed and exhaust fan speed can be set independently.
1
Button operation
Commissioning menu 1/2
Initial setting
Airflow
Auto bypass
External input
Service
Cursor
Page
Main menu:
Airflow
Loading
F1
F2
F3
F4
Address
Airflow
Select:
M-NET address
All
Accessing the «Airflow» screen
Select “Airflow” from the Main menu >
Commissioning, and press the
button.
Select the address of the unit.
The address selection screen will appear.
Press the or button to select the M-NET
address number of the unit. When choosing same
setting to all Lossnay units connected with the
controller, select the address to “All”.
The product data is loaded before the screen
will appear. [Loading] is displayed. (10 to 60
seconds)
P
Main
OFF
Detailed function setting