OCH707C
SW2 setting
Display detail
Explanation for display
Unit
°C
Indoor pipe temperature / Liquid (TH2)
on error occurring
- 39 to 88
- 39 to 88
(When the temperature is 0 °C or less, “–” and
temperature are displayed by turns.)
(Example) When -15 °C;
0.5 s 0.5 s 2 s
Indoor pipe temperature / Cond./ Eva.
(TH5) on error occurring
- 39 to 88
- 39 to 88
(When the temperature is 0 °C or less, “–” and
temperature are displayed by turns.)
(Example) When -15 °C;
0.5 s 0.5 s 2 s
Outdoor 2-phase pipe (TH6) on error
occurring
- 39 to 88
- 39 to 88
(When the temperature is 0 °C or less, “–” and
temperature are displayed by turns.)
(Example) When -15 °C;
0.5 s 0.5 s 2 s
Outdoor ambient temperature (TH7) on
error occurring
- 39 to 88
- 39 to 88
(When the temperature is 0 °C or less, “–” and
temperature are displayed by turns.)
(Example) When -15 °C;
0.5 s 0.5 s 2 s
Outdoor heatsink temperature (TH8) on
error occurring
- 40 to 200
- 40 to 200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
15
15
°C
°C
°C
The black square ( ) indicates a switch position.
1
ON
2 3 4 5 6
°C
0 to 255
(When the temperature is 100 °C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150 °C;
0.5 s 0.5 s 2 s
1
ON
2 3 4 5 6
Discharge superheat on error occurring
SHd
0 to 255
SHd = TH4 - TH6
50
1
Thermo-on time until error stops
0 to 999
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 s 0.5 s 2 s
1
ON
2 3 4 5 6
Minute
15
4
°C