39
OCH707C
9-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is ON>
Note: Refer to indoor unit section for code P and code E.
Check
code
Abnormal points and detection method
Cause
Judgment and action
None
—
1
No voltage is supplied to termi-
nal block (TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or disconnec-
tion of power supply terminal
c) Open phase (L, L2 or N
phase)
2
Electric power is not supplied
to power supply terminal of out-
door power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
(Disconnection of terminal
on outdoor power circuit
board)
3
Electric power is not supplied
to outdoor controller circuit
board.
a) Disconnection of connector
(CNDC)
4
Disconnection of reactor (DCL
or ACL)
5
Disconnection of outdoor power
circuit board (PUZ-M·VKA)/
outdoor noise filter circuit board
(PUZ-M·YKA) or parts failure
in outdoor power circuit board
(PUZ-M·VKA)/outdoor noise
filter circuit board (PUZ-M·YKA)
6
Defective outdoor power circuit
board
7
Open of rush current protect
resistor (RS) (PUZ-M·YKA)
8
Defective outdoor controller
circuit board
1
Check following items.
a) Power supply breaker
b) Connection of power supply terminal
block. (TB1)
c) Connection of power supply terminal
block. (TB1)
2
Check following items.
a) Connection of power supply terminal block.
(TB1)
b) Connection of terminal on outdoor power
circuit board.
3
Check
connection of the connector (CNDC)
on the outdoor controller circuit board.
Refer to "9-9. TEST POINT DIAGRAM".
4
Check
connection of reactor. (DCL or ACL)
Refer to "6. WIRING DIAGRAM".
5
a) Check connection of outdoor power circuit
board (PUZ-M·VKA)/outdoor noise filter
circuit board (PUZ-M·YKA).
b) Replace outdoor power circuit board
(PUZ-M·VKA)/outdoor noise filter circuit
board (PUZ-M·YKA).
Refer to "9-9. TEST POINT DIAGRAM".
6
Replace outdoor power circuit board.
7
Replace rush current protect resistor (RS)
* Power circuit board might be short-circuit.
Check the power circuit board. (Refer to
"9-9. TEST POINT DIAGRAM")
8
Replace controller board (When items
above are checked but the units cannot be
repaired.)
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power sup-
ply.
63H: High pressure switch
1
Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2
Disconnection or contact failure
of 63H
3
63H is working due to defective
parts.
4
Defective outdoor controller
circuit board
1
Check connection of 63H connector on
outdoor controller circuit board.
Refer to "9-9. TEST POINT DIAGRAM".
2
Check the 63H side of connecting wire.
3
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.