9

2

Wiring examples

• Controller name, symbol and allowable number of controllers.

2. M-NET Remote control cables

A

 : Power source

B

 : Transmission line

Name

Outdoor unit controller
Indoor unit controller

Remote controller

Symbol

OC

IC

RC

(M-NET)

MA

Allowable number of controllers

One to eight controllers for one OC
Maximum of 16 controllers for one
OC
Maximum of two per group

6.2. Control box and connecting position of wiring

(Fig. 6-1)

1. Connect the indoor unit transmission line to transmission terminal block (TB3), or

connect the wiring between outdoor units or the wiring with the centralized con-
trol system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the indoor unit transmis-

sion line to the earth screw (

) and connect shield ground of the line between

outdoor units and the central control system transmission line to the shield (S)
terminal of the centralized control terminal block (TB7) shield (S) terminal. In
addition, in the case of outdoor units whose power supply connector CN41 has
been replaced by CN40, the shield terminal (S) of terminal block (TB7) of the

centralized control system should also be connected to the ground (

).

2. Conduit mounting plates (ø27 [1-1/16 inch]) are being provided. Pass the power

supply and transmission wires through the appropriate knock-out holes, then re-
move the knock-out piece from the bottom of the terminal box and connect the wires.

3. Fix power source wiring to terminal box by using buffer bushing for tensile force

(PG connection or the like).

6.3. Wiring transmission cables

1

Types of control cables

1. Wiring transmission cables
• Types of transmission cables: Shielding wire CVVS or CPEVS
• Cable diameter: More than 1.25 mm

2

 [AWG16]

• Maximum wiring length: Within 200 m [656 ft]

Fig. 6-1

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are

necessary.)

<Examples of Transmission Cable Wiring>

M-NET Remote Controller (Fig. 6-2)

MA Remote Controller (Fig. 6-3)

<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2

and terminal S on the transmission cable block of the indoor unit (IC).

c.

Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).

d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. The jumper connector CN41 on the control panel does not change.

f.

Connect the terminal S on the terminal block for central control  for the power supply unit  to the ground terminal (

) in the electrical component box.

g. Set the address setting switch as follows.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)

Outdoor Unit

51 to 100

Use the most recent address of all the indoor units plus 50
* The address automatically becomes “100” if it is set as “01 - 50”.

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

<Permissible Lengths>

1

M-NET Remote controller

Max length via outdoor units: L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

3

+L

5

 and L

1

+L

2

+L

6

+L

7

 

=

 500 m [1640 ft] (1.25 mm

2

 [AWG16] or more)

Max transmission cable length: L

and L

3

+L

4

 and L

3

+L

5

 and L

6

 and L

2

+L

6

 and L

7

 

=

 200 m [656 ft] (1.25 mm

2

 [AWG16] or more)

Remote controller cable length:

r

1

r

2

r

2

 +

r

3

,

r

4

  

=

 10 m [33 ft] (0.5 to 1.25 mm

2

 [AWG20 to AWG16])

If the length exceeds 10 m [33 ft], use a 1.25 mm

2

 [AWG16] shielded wire.  The length of this section (L

8

) should be included in the

calculation of the maximum length and overall length.

2

MA Remote controller

Max length via outdoor unit (M-NET cable): L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

6

+L

7

 

=

 500 m [1640 ft] (1.25 mm

2

 [AWG16] or more)

Max transmission cable length (M-NET cable): L

and L

3

+L

4

 and L

6

 and L

2

+L

6

 and L

7

 

=

 200 m [656 ft] (1.25 mm

2

 [AWG16]

 

or more)

Remote controller cable length:

c

1

 and 

c

1

+

c

2

 +

c

3

 and 

c

1

+

c

2

+

c

3

+

c

4  

=

 200 m [656 ft] (0.3 to 1.25 mm

2

 [AWG20 to AWG16])

6. Electrical work

M1

S

M2

A

B

M1

S

M2

L1 L2 GR

TB3

TB7

Kind of remote control cable

Cable diameter

Remarks

Shielding wire MVVS
0.5 to 1.25 mm

 [AWG20 to AWG16]

When 10 m  [32 ft] is exceeded, use cable with
the same specifications as transmission line wir-
ing

3. MA Remote control cables

Kind of remote control cable

Cable diameter

2-core cable (unshielded)
0.3 mm

2

 (AWG22) to 1.25 mm

2

 (AWG16)

CONDUIT PLATE : accessory

Содержание PUMY-P36NHMU

Страница 1: ...l MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR For use with R410A Français MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre ...

Страница 2: ...frig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repa...

Страница 3: ... or moisture enters the refrig erant lines refrigeration oil deterioration may result Do not use a charging cylinder If a charging cylinder is used the composi tion of the refrigerant will change and the efficiency will be lowered 2 Installation location 2 1 Refrigerant pipe Refer to Fig 4 1 2 2 Choosing the outdoor unit installation location Avoid locations exposed to sources of heat Select a loc...

Страница 4: ... 500 mm 19 11 16 inch or more 6 Obstacles at rear sides and above only Fig 2 7 Do not install the optional air outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm 13 32 inch space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9 No more than three units must be installed side by side In addition leave space ...

Страница 5: ... on site Warning The unit must be securely installed on a structure that can sustain its weight If the unit is mounted on an unstable structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may fall down and cause damage or injuri...

Страница 6: ...ring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements A mm inch Å Liquid pipe ı Gas pipe PUMY ø9 52 3 8 ø15 88 5 8 B C D mm inch Ç Total capacity of indoor units Å Liquid pipe ı Gas pipe ø9 52 3 8 ø15 88 5 8 a b c d e f mm inch Î Model number Å Liquid pipe ı Gas pipe P06 P08 P12 P15 P18 ø6 35 1 4 ø12 7 1 2 P24 P30 P36 P48 P54 ø9 52 3 8 ø15 88 5 8 Branch ki...

Страница 7: ... surrounding temperature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1 C 1 8 F the pressure will change by about 0 01 MPa 1 5 PSIG Make the necessary corrections 4 If the pressure decreases in steps 2 or 3 there is a gas leak Look for the source of ...

Страница 8: ...s sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connected electrical parts will be burnt out 6 Use 2 core shield cable for transmission line If transmission lines of different systems are wired with the same multiplecore cable the resultant poor transmit ting and receiving will cause erroneous operations 6 Electrical w...

Страница 9: ...the transmission cable terminal block of the indoor unit IC that has the most recent address within the same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the outdoor unit OC e The jumper connector CN41 on the control panel does not change f Connect the terminal S on the terminal block for...

Страница 10: ...r than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire 30 A 30 mA 0 1 sec or less 30 A 5 3 AWG10 5 3 AWG10 Indoor Unit Main Cable 2 Minimum Wire Thickness mm2 AWG Breaker for Current Leakage Model Outdoor Unit P36 P48 Breaker for Wiring 1 Ground 6 Electrical work Thickness of Wire for Main Power Supply and On...

Страница 11: ...manifold valve and put the cap back onto each stop valve Note 1 Never carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant ex ceeds the amount of charge less refrigerant will cause an extreme pres sure rise and may result in an accident 2 Do not contin...

Страница 12: ...220 y tubos de aleación de cobre sin costuras para conectar los tubos del refrigerante Si los tubos no se co nectan correctamente la unidad no estará bien puesta a tierra y puede pro vocar descargas eléctricas Utilice sólo cables especificados para el cableado Las conexiones se deben realizar con seguridad sin corriente en los terminales Si los cables no están bien conectados o no se han instalado...

Страница 13: ...n refrigerante R22 Sustituya las tuercas de abocardado existentes y vuelva a abocardar las seccio nes abocardadas No use tuberías de poco grosor Consulte la página 15 Almacene las tuberías que se deban instalar en el interior y mantenga los orificios tapados hasta el momento de instalarlas Deje las juntas articula das y otras piezas en sus embalajes Si el polvo los restos o la humedad entran en la...

Страница 14: ...ólo en la parte trasera y superior Fig 2 9 No se deben instalar más de tres unidades correlativas Además se debe dejar el espacio indicado No utilice las guías para salida de aire opcionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 10 Si utiliza una guía para salida de aire opcional el espacio libre deberá ser de 1000 mm 39 3 8 inch o más 4 Obstáculos sólo ...

Страница 15: ...le con otro tipo de refrigerante y vacíe completamente de aire los tubos El aire que quede en los tubos puede provocar picos de presión que causarían su rotura y otros daños Tipo de unidad interior P06 P18 P24 P54 Tubo de líquido ø6 35 mm 1 4 inch ø9 52 mm 3 8 inch grosor 0 8 mm 1 32 inch grosor 0 8 mm 1 32 inch Tubo de gas ø12 7 mm 1 2 inch ø15 88 mm 5 8 inch grosor 0 8 mm 1 32 inch grosor 1 0 mm...

Страница 16: ...te Cuando utilice un sellador de tubos normal consulte la Tabla 1 para abocardar tuberías para refrigerante R410A Para confirmar las medidas de A se puede utilizar el ajustador del tamaño A mm inch Å Tubo de líquido ı Tubo de gas PUMY ø9 52 3 8 ø15 88 5 8 B C D mm inch Ç Capacidad total de las unidades interiores Å Tubo de líquido ı Tubo de gas ø9 52 3 8 ø15 88 5 8 a b c d e f mm inch Î Número de ...

Страница 17: ...n no se ha reducido 3 Presurice a 3 8 MPa 550 PSIG y tome la temperatura ambiental y la presión del refrigerante 3 Si la presión especificada se mantiene estable durante un día y no se reduce las tuberías han pasado la prueba y no existe riesgo de fugas Si la temperatura ambiental cambia 1 C 1 8 F la presión variará unos 0 01 MPa 1 5 PSIG Haga las correcciones necesarias 4 Si la presión se reduce ...

Страница 18: ...uando se realiza el trabajo de man tenimiento 5 No conecte nunca la fuente principal de energía al bloque de terminal de la línea de transmisión Si está conectado las piezas eléctricas se quemarán 6 Use cable blindado de dos almas para la línea de transmisión Si las líneas de transmisión de sistemas diferentes están conectados con los mismos cables de varias almas la pobre transmisión y recepción ...

Страница 19: ...s IC que no sea el de IC máster IC máster debe ser secuencial Unidad exterior de 51 a 100 Ajuste la dirección más reciente de las unidades interiores en el mismo sistema de refrigeración 50 La dirección se establece automáticamente en 100 si se configura como 01 50 M NET R C máster de 101 a 150 Ajuste la dirección IC máster 100 M NET R C subordinada de 151 a 200 Ajuste la dirección IC máster 150 M...

Страница 20: ... fuga de tierra Si no se instala un disyuntor de fuga de tierra puede producirse un electroshock Use los fusibles y el disyuntor con la capacidad correcta Si emplea un fusible o cable con demasiada capacidad puede haber una disfunción de la unidad o incluso puede producirse un incendio 6 Trabajo eléctrico Grosor del cable para el suministro principal de energía y capacidades on off 6 4 Cableado de...

Страница 21: ...cio exterior SW2 4 de ON a OFF 8 Extraiga la válvula distribuidora del medidor y vuelva a colocar el tapón a cada válvula de parada Notas 1 Nunca realice el vaciado si la cantidad de refrigerante del interior de la unidad interior es superior a la cantidad de refrigerante no cargado Si realiza este procedimiento cuando la cantidad de refrigerante es supe rior a la cantidad de refrigerante sin carg...

Страница 22: ...duire N utiliser que les câbles spécifiés pour les raccordements Les connexions doi vent être correctement effectuées sans tension sur les bornes Si les câbles ne sont pas correctement connectés ou installés une surchauffe ou un incendie peut se produire Le couvercle du bloc de sortie de l appareil extérieur doit être solidement fixé S il n est pas correctement installé et si des poussières et de ...

Страница 23: ...éléphoniques Une mise à la terre incorrecte de l appareil peut provoquer un choc électrique Utiliser des coupe circuits disjoncteur de fuite à la terre interrupteur d isolement fusi ble B et disjoncteur à boîtier moulé à la capacité spécifiée Si la capacité du coupe circuit est supérieure à celle spécifiée une défaillance ou un incendie peut se produire Ne pas toucher les interrupteurs les mains h...

Страница 24: ...s Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit d air vers le haut 3 Obstacles uniquement à l avant Fig 2 10 Lors de l utilisation d un guidage de sortie d air en option le jeu est de 1000 mm 39 3 8 inch minimum 4 Obstacles uniquement à l avant et à l arrière Fig 2 11 Lors de l utilisation d un guidage de sortie d air en option ...

Страница 25: ...mélanger avec un autre réfrigérant et faire le vide d air dans les tuyaux La présence d air dans les tuyaux peut provoquer des pointes de pression entraînant une rupture et d autres risques Type d appareil intérieur P06 P18 P24 P54 Conduit de liquide ø6 35 mm 1 4 inch ø9 52 mm 3 8 inch épaisseur 0 8 mm 1 32 inch épaisseur 0 8 mm 1 32 inch Conduit de gaz ø12 7 mm 1 2 inch ø15 88 mm 5 8 inch épaisse...

Страница 26: ...e d huile réfrigérante application sur site Si un procédé d étanchéité traditionnel est utilisé pour les tuyaux se reporter au tableau 1 pour l évasement des tuyaux de réfrigérant R410A La jauge de réglage de la taille peut être utilisée pour confirmer les mesures A A mm inch Å Conduit de liquide ı Conduit de gaz PUMY ø9 52 3 8 ø15 88 5 8 B C D mm inch Ç Puissance totale des appareils intérieurs Å...

Страница 27: ...nt ou d être endommagé à cause d une infiltration d eau et de poussières A Vanne d arrêt côté liquide B Vanne d arrêt côté gaz C Orifice pour l entretien D Section d ouverture fermeture E Tuyau local A Couvercle de la tuyauterie avant B Couvercle de la tuyauterie C Vanne d arrêt D Panneau de service E Rayon de cintrage 100 mm 150 mm F Hermétique idem pour le côté gaz G Fourrure du tuyau H Ne pas u...

Страница 28: ...5 Ne jamais raccorder la source d alimentation principale au bloc terminal de la ligne de transmission car cela brûlerait les composants électriques 6 Utiliser un câble blindé à deux fils comme ligne de transmission Si les lignes de trans mission des différents systèmes devaient être reliées par le même câble à fils multi ples la transmission et la réception seraient mauvaises ce qui conduirait à ...

Страница 29: ...eils extérieurs OC e Le cavalier CN41 du panneau de commande ne change pas f Raccorder la borne S du bloc de sorties du contrôle centralisé de l unité d alimentation à la borne de terre du boîtier des composants électriques g Régler les commutateurs d adresses comme indiqué ci dessous 6 Installations électriques 2 Câbles de la télécommande M NET Type de câble de télécommande Diamètre du câble Rema...

Страница 30: ...ce coupe circuit n est pas installé il peut y avoir danger d électrocu tion Ne jamais utiliser de coupe circuits ou de fusibles autres que ceux possédant la valeur adéquate L utilisation de fusibles et de fils fils en cuivre surdimensionnés risque de provoquer un mauvais fonctionnement de l appareil voir un incendie 6 Installations électriques Section des câbles pour l alimentation principale et c...

Страница 31: ...la vanne collective à jauge et remettre le capuchon en place sur chacune des vannes d arrêt Remarque 1 Ne jamais procéder au pompage si la quantité de réfrigérant dans l appareil inté rieur est supérieure à la quantité de réfrigérant sans charge supplémentaire Le pompage lorsque la quantité de réfrigérant dépasse la quantité de réfrigérant sans charge provoquera une forte augmentation de pression ...

Страница 32: ... on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U872H02 ...

Отзывы: