Job Name:
Drawing Reference:
Schedule No.
System No.:
Notes:
OUTDOOR VRF SYSTEM
SPECIFICATIONS
Capacity
Cooling……………………………………………..36,000 Btu/h
Heating……………………………………………..40,000 Btu/h
Power
Power Source……………….........208 / 230V, 1-phase, 60Hz
Power Input
Cooling………………………………………………3.22 kW
Heating………………………………………………2.93 kW
Current
Cooling (208 / 230)........................................14.2 / 15.7 A
Heating (208 / 230) ...................................…12.9 / 14.2 A
Minimum Circuit Ampacity (MCA) (208 / 230)….……..…26 A
Breaker Size for Wiring ........................................….......30 A
External Finish
………Pre-coated Galvanized-steel Sheets
Munsell No. 3Y 7.8 / 1.1
External Dimensions
Inches………………..53-3/16 h x 37-7/16 w x 13 (+1-3/16) d
mm……………………………..1,350 h x 950 w x 330 (+30) d
Net Weight
………………………………….287 lbs. / 130 kg
Fan
Type x Quantity...………..............................Propeller Fan x 2
Airflow Rate
……………………………………...……3,530 cfm
Motor Output……...…..………………………0.086 + 0.086 kW
Compressor
Type………………...................………….Inverter-driven Scroll
Motor Output………..…………………………………….2.2 kW
Lubricant
………………..…...………………………….FV50S
Refrigerant
……………..…...…………………………..R410A
Protection Devices
High Pressure Protection………………High Pressure Switch
Compressor…………Discharge Thermo / Overcurrent Detection
Fan…...…………………………..Overheat / Voltage Protection
Piping Diameter
Liquid (High Pressure)………..……………3/8" / 9.52 mm Flare
Gas (Low Pressure)………………………5/8" / 15.88 mm Flare
Indoor Unit
Total Capacity…..…….50% –130% of Outdoor Unit Capacity
Model / Quantity…………………..…………..….P06-P36 / 1 ~ 6
Sound Level (Cooling / Heating)
………….49 / 51 dB(A)
Operating Temperature Range
Cooling (Outdoor)……………….23°F ~ 115°F (-5° ~ +46°C) DB*
Heating (Outdoor)…………….0°F ~ +60°F (-18° ~ +15°C) WB
Anti-corrosion Protection
Blue Fin Treatment
applied to condenser coil protects coil
from airborne contaminants.
Seacoast Protection
External Panel Base: Steel sheets with aluminum-zinc-
magnesium coating on external and internal surfaces
External Panel (Top, Front, Back): Galvanized steel sheets
with acrylic- and polyester-resin coating on external and
internal surfaces
Fan Motor Support: Galvanized-steel sheets with epoxy-
resin coating applied to external surface
Separator and Valve Bed: Galvanized-steel sheets with
epoxy-resin coating
Options
□
Branch Joint (T-Branch)…………………..…....CMY-Y62-G-E
□
Header - Four-Branch…………………………….CMY-Y64-G-E
□
Header - Eight-Branch……………………………..CMY-Y68-G-E
□
Drain Pan………………………………….….….PAC-SG64DP-E
□
Drain Socket………………………………….….PAC-SG61DS-E
•
•
•
•
Model:
PUMY-P36NHMU (-BS)
OUTDOOR VRF
SYSTEM FEATURES
ti
n
u
r
o
o
d
t
u
o
e
s
a
h
p
-
e
l
g
n
i
S
•
with variable refrigerant
flow (VRF)
technology
• In
verter-driven (variable
speed) compressor
•
Total refrigerant piping
length of 394' (120 m)
• Uses CITY MU
L
TI indoo
r
units and Controls Net
work