72
10
ELECTRICAL WIRING
10-1. OVERVIEW OF POWER WIRING
10-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY
10-2-1. Wiring diagram for main power supply
10-2-2. Power supply wire diameter and capacity
This chapter provides an introduction to electrical wiring for the MULTI-S series, together with notes concerning power wiring,
wiring for control (transmission wires and remote controller wires), and the frequency converter.
(1) Please refer to your electric power company about the indoor wiring specifications for the power wire diameter
and capacity of protective devices (switches and leakage of breakers).
(2) Taking into consideration voltage drops caused by the length of the wires when operating devices installed
downstream, determine the specifications of wires able to handle the maximum current or voltage. In addition,
protective devices must be able to protect against current leakage or excessive current.
(3) It is generally necessary to include leakage breakers when installing wiring for the CITY MULTI-S series.
Protective switches (excessive current protection) along main or branch lines should typically consist of fuse-less
breakers (ELB).
(4) Please perform grounding.
(5) It is suggested that you consult with your electric power company concerning restrictions on electrical specifications.
Outdoor unit
Grounded
Circuit breaker
Power supply
single phase
220-230-240V, 50Hz
Outdoor unit
Indoor unit
Grounded
Grounded
Junction box
Circuit breaker
N
Power supply
(3phase 380-400-415V, 50Hz)
• PUMY-P125VMA
• PUMY-P125YMA
PUMY-P125YMA
1
Circuit breaker
Power supply
single phase
50Hz 220-230-240V
Interrupting current
Grounded
Minimum wire cross section area(mm
2
)
Breaker
Model
Branch line
Main line
PUMY-P125VMA
PUMY-P125YMA
PUMY-P125YMA
1
Performance characteristic
25A,30mA for 0.1 sec. or less
Outdoor unit
Interrupting current
15A
Grounded
[
1.6
Minimum wire cross section area(mm)
Breaker
Model
Branch line
–
Main line
[
1.6
All Models
Performance characteristic
15A, 30mA for 0.1 sec. or less
Indoor unit
5.5(6)
2.5
5.5(6)
2.5
—
—
32A
25A
32A,30mA for 0.1 sec. or less