7.2.  Test run

7.2.1.  Using remote controller 

Refer to the indoor unit installation manual.

•  Be sure to perform the test run for each indoor unit. Make sure each indoor 

unit operates properly following the installation manual attached to the unit.

•  If you perform the test run for all indoor units at once, you cannot detect any 

erroneous connection, if any, of the refrigerant pipes and the connecting wires.

*  The compressor operation is not available for 3 minutes at least after the power 

is supplied.

•  The compressor can emit noise just after turn on the power supply or in case 

of low outside air temperature.

•  Depending on the operating conditions, the outdoor unit fan may stop while 

the compressor is operating, but this is not a malfunction.

7.3.  Refrigerant collecting (Pump down)

Perform the following procedures to collect the refrigerant when moving the indoor 

unit or the outdoor unit.

1

  Turn off the circuit breaker.

2

  Connect the low pressure side of the gauge manifold to the service port of the 

gas side stop valve.

3

  Close the liquid stop valve.

4

  Supply power (circuit breaker). 

*  Start-up of the indoor-outdoor communication takes about 3 minutes after the 

power (circuit breaker) is turned on. Start the pump-down operation 3 to 4 minutes 

after the power (circuit breaker) is turned ON.

5

  Perform the test run for cooling operation (SW3-1: ON and SW3-2: OFF). The 

compressor (outdoor unit) and ventilators (indoor and outdoor units) start operating 

and test run for cooling operation begins. After the cooling operation has been 

carried out for approximately five minutes, set the outdoor service switch SW2-4 

(pump down switch) from OFF to ON. 

*  Do not continue to operate for a long time with the switch SW2-4 set to ON. Make 

sure to switch it to OFF after pump down is completed.

*  Only set the SW3-1 to ON if the unit is stopped. However, even if the unit is 

stopped and the SW3-1 is set to ON less than 3 minutes after the compressor 

stops, the refrigerant collecting operation cannot be performed. Wait until the 

compressor has been stopped for 3 minutes and then set the SW3-1 to ON again. 

*  When connecting a Cylinder or Hydrobox unit, do not use the DipSW functions 

of outdoor unit. Operate all of the indoor units, excluding a Cylinder or Hydrobox 

unit, in cooling mode. 

6

  Fully close the gas stop valve when the pressure reading on the gauge drops 

0.05 - 0.00 MPa (approximately 0.5 - 0.0 kgf/cm

2

)

7

  Stop the air conditioner operation (SW3-1: OFF). Set the outdoor service switch 

SW2-4 from ON to OFF.

*  When connecting a Cylinder or Hydrobox unit, stop the indoor units operation. 

8

  Turn off the power supply (circuit breaker). 

*  If too much refrigerant has been added to the air conditioner system, the pres-

sure may not drop to 0.05 MPa (0.5 kgf/cm

2

). If this occurs, use a refrigerant 

collecting device to collect all of the refrigerant in the system, and then recharge 

the system with the correct amount of refrigerant after the indoor and outdoor 

units have been relocated.

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect-

ing the refrigerant pipes. The compressor may burst and cause injury if any 

foreign substance, such as air, enters the system.

7.1.  Before test run

►  After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 

or control wiring, wrong polarity, and no disconnection of one phase in the 

supply.

►  Use a 500-volt M-ohm tester to check that the resistance between the power 

supply terminals and ground is at least 1 MΩ.

►  Do not carry out this test on the control wiring (low voltage circuit) terminals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1 MΩ.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 

period, the insulation resistance will drop below 1 MΩ due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.

1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 MΩ, the compressor is faulty or the resistance 

dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 

measure the insulation resistance again.

  •  The insulation resistance drops due to accumulation of refrigerant in the com-

pressor. The resistance will rise above 1 MΩ after the compressor is warmed 

up for 12 hours.

    (The time necessary to warm up the compressor varies according to atmospheric 

conditions and refrigerant accumulation.)

  •  To operate the compressor with refrigerant accumulated in the compressor, the 

compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 MΩ, the compressor is not faulty.

 Caution:

  The compressor will not operate unless the power supply phase connection 

is correct.

•  Turn on the power at least 12 hours before starting operation.

-  Starting operation immediately after turning on the main power switch can result 

in severe damage to internal parts. Keep the power switch turned on during the 

operational season.

►  The followings must be checked as well.

•  The outdoor unit is not faulty. LED on the control board of the outdoor unit flash 

when the outdoor unit is faulty.

•  Both the gas and liquid stop valves are completely open.

7.  Test run

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor 

will not operate for 3 minutes to protect the air conditioner.

7.2.2.  Using SW3 in outdoor unit

Note:

In case of the test run from outdoor unit, all indoor units operate. Therefore, 

you can not detect any erroneous connection of refrigerant pipes and the 

connecting wires. If it aims at detection of any erroneous connection, be sure 

to carry out the test run from remote controller with reference to “7.2.1. Using 

remote controller.”

SW3-1

ON

Cooling operation

SW3-2

OFF

SW3-1

ON

Heating operation

SW3-2

ON

*  After performing the test run, set SW3-1 to OFF.

•  A few seconds after the compressor starts, a clanging noise may be heard from 

the inside of the outdoor unit. The noise is coming from the check valve due to the 

small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW3-2 during 

the test run. (To change the test run operation mode during the test run, stop 

the test run by DIP switch SW3-1. After changing the test run operation mode, 

resume the test run by switch SW3-1.)

BH79D826H05.indb   22

2020/04/27   9:37:02

024

Содержание PUMY-P112VKM4

Страница 1: ...A ile beraber kullanmak için MONTÖR İÇİN MONTAJ ELKİTABI Emniyetli ve doğru kullanım için klima cihazını monte etmeden önce bu kılavuzu ve iç ünite montaj kılavuzunu tamamıyla okuyun Türkçe INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English BH79D826H05 indb 1 2020 04 27 9 36 53 001 ...

Страница 2: ...елі а потім мову bg Посетете горепосочения уебсайт за да изтеглите ръководства като изберете име на модел и след това език pl Odwiedź powyższą stronę internetową aby pobrać instrukcje wybierz nazwę modelu a następnie język cs Příručky naleznete ke stažení na internetové stránce zmíněné výše poté co zvolíte model a jazyk sk Na webovej stránke vyššie si môžete stiahnuť návody Vyberte názov modelu a ...

Страница 3: ...Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown In the worst cas...

Страница 4: ...oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Flare tool Charge hose Size ...

Страница 5: ...trictions Only 1 PWFY P100VM E AU can be connected PWFY P200VM E AU and PWFY P100VM E BU cannot be connected The PWFY unit cannot be the only unit connected to an outdoor unit Select an outdoor unit so that the total rated capacity of the indoor units excluding the PWFY unit is 50 100 of the outdoor unit capacity Limits for the total rated capacity of the indoor units when connecting a PWFY unit P...

Страница 6: ...ss than 7 C the flow temperature and blow off temperature are lowered When operating a Cylinder or Hydrobox unit in the DHW mode and operating ATA indoor units at the same time the outdoor temperature must be 7 C or more When the outdoor temperature is less than 7 C they cannot operate at the same time 2 5 3 Switch settings When connecting a Cylinder or Hydrobox unit to a PUMY unit set the DIP swi...

Страница 7: ...rd airflow 2 9 2 When installing multiple outdoor units Leave 25 mm space or more between the units 1 Obstacles at rear only Fig 2 9 2 Obstacles at rear and above only Fig 2 10 No more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 11 When using an optional air outlet ...

Страница 8: ...rder to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may fall down and cause damage or injuries Caution Install unit on a rigid structure to prevent excessive operation sound or vibra tion Fig 3 1 A M10 3 8 bolt B Base C As long as possible D Vent E Set deep in the ground 4 Installing the refrigerant piping 4 1 Precautions for devices that us...

Страница 9: ...or unit and branch box and outdoor unit sides Remove the valve cover of the outdoor unit then connect the pipe Refrigerant pipes are used to connect the branch box and outdoor unit Fig 4 2 B C B C C C C C C C L r h2 b2 b1 c1 a6 a5 a4 a3 a2 h3 h1 H a1 a7 a8 D A A Outdoor unit B Branch box C Indoor unit D First joint Permissible length one way Total piping length c1 b1 b2 a1 a2 a3 a4 a5 a6 a7 a8 150...

Страница 10: ... B d1 c1 L2 L1 c2 b2 b1 h1 h2 H h3 C D D a1 a2 a3 a4 a5 a6 a7 a8 a9 a10 a11 E E E F F F F F F F F A Outdoor Unit B First joint C Branch header D Branch box E CityMulti Indoor unit F M S P series Indoor unit Cylinder unit or Hydrobox unit PKFY P VBM PKFY P10 32VLM PFFY P VKM PFFY P VCM and PFFY P VL type indoor units cannot be used in a mixed system Permissible length One way Total piping length d1...

Страница 11: ...ze Outdoor unit Branch box Liquid pipe Gas pipe PUMY P112 140 ø9 52 ø15 88 Pipe size Branch box Indoor unit Case of M series or S series Indoor unit 1 Indoor unit series Model number Liquid pipe Gas pipe M series or S series 15 42 ø6 35 ø9 52 50 ø6 35 ø12 7 60 ø6 35 ø15 88 71 80 ø9 52 ø15 88 P series 35 50 2 ø6 35 ø12 7 60 100 ø9 52 ø15 88 Cylinder unit ø9 52 ø15 88 Hydrobox unit 1 The lineup of a...

Страница 12: ... Model number Liquid pipe Gas pipe CityMulti 10 50 ø6 35 ø12 7 63 140 ø9 52 ø15 88 M series or S series 15 42 ø6 35 ø9 52 50 ø6 35 ø12 7 60 ø6 35 ø15 88 71 80 ø9 52 ø15 88 P series 35 50 1 ø6 35 ø12 7 60 100 ø9 52 ø15 88 Cylinder unit ø9 52 ø15 88 Hydrobox unit 2 branch joint CMY Y62 G E 4 branch header CMY Y64 G E 8 branch header CMY Y68 G E 1 When using 35 50 type indoor unit of P series use the...

Страница 13: ...torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 3 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements Warning When installing the unit securely connect the refrigerant pipes before starting the compressor To connect the CONNECTION KIT P...

Страница 14: ... 2 or 3 there is a gas leak Look for the source of the gas leak 4 7 Stop valve opening method 1 Gas side Fig 4 11 1 Remove the cap pull the handle toward you and rotate 1 4 turn in a counterclock wise direction to open 2 Make sure that the stop valve is open completely push in the handle and rotate the cap back to its original position 2 Liquid side Fig 4 12 1 Remove the cap and turn the valve rod...

Страница 15: ... M series indoor unit refer to the installation manual for the CONNECTION KIT 1 When connecting a branch box be sure to turn on the indoor units and the branch box before turning on the outdoor unit 4 8 Additional refrigerant charge Additional refrigerant charge Refrigerant for the extended piping is not included in the outdoor unit when the unit is shipped from the factory Therefore charge each r...

Страница 16: ... at the same time Use a WMA remote controller for the PWFY unit For details refer to the installation manual for the PWFY unit j When connecting a Cylinder or Hydrobox unit Do not perform the group settings for the Cylinder or Hydrobox unit and the other indoor units Wiring Method and Address Setting include Branch box system Please refer to the Branch box Installation Manual 6 Electrical work M1 ...

Страница 17: ...tdoor units M NET cable L1 L2 L3 L4 L5 500 m 1 25 mm2 or more Max transmission cable length M NET cable L1 L2 L3 L4 L5 200 m 1 25 mm2 or more Max transmission cable length A control cable L6 25 m 1 5 mm Remote controller cable length m1 200 m 0 3 to 1 25 mm 01 06 M NET Remote Controller MA Remote Controller Fig 6 3 Fig 6 2 A Group 1 B Group 2 C Group 3 D Shielded Wire E Sub Remote Controller Addre...

Страница 18: ...A IC A IC A IC MA RC WL RC 3 branch type 2 Group operation between different refrigerant systems C O C O BC A B C BC A B C NO A IC A IC A IC MA RC WL RC 3 branch type 3 branch type 4 Group operation between A control system and M NET control system OC BC A B C D E A IC A IC A IC A IC WL RC WL RC WL RC WL RC M IC MA RC A IC NO 5 branch type NO OC BC A B C D E M NET RC A IC MA RC MA RC WL RC WL RC W...

Страница 19: ...Branch Box Example Fig 6 6 PUMY P VKM5 Fig 6 6 A B E E F A PUMY P YKM E 4 N 220 230 240 V 50 Hz N 220 230 V 60 Hz YKM4 3N 380 400 415 V 50 Hz 3N 380 V 60 Hz YKME4 3N 380 400 415 V 50 Hz N 220 230 240 V 50 Hz N 220 230 V 60 Hz E E F A N 220 230 240 V 50 Hz N 220 230 V 60 Hz A Switch Breakers for Wiring and Current Leakage B Outdoor Unit C Branch Box D A Control Indoor Unit M S P series indoor unit ...

Страница 20: ...n power is supplied separately Model Power Supply Minimum Wire Cross sectional area mm2 Breaker for Wiring 1 Breaker for Current Leakage Main Cable Ground Outdoor Unit P112 140VKM5 N 220 230 240 V 50 Hz N 220 230 V 60 Hz 6 6 32 A 32 A 30 mA 0 1 sec or less P112 140YKM4 3N 380 400 415 V 50 Hz 2 3N 380 V 60 Hz 1 5 1 5 16 A 16 A 30 mA 0 1 sec or less P112 140YKME4 3N 380 400 415 V 50 Hz 2 When power ...

Страница 21: ...te that generated overcurrent may include some amount of direct current Be sure to attach the terminal block covers panel of the outdoor unit securely If it is not attached correctly if could result in a fire or an electric shock due to dust water etc Caution Be careful not to make mis wiring Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly ...

Страница 22: ...ss Start address 2 03 D port address Start address 3 04 E port address Start address 4 05 3 Branch Box 2 Branch Box 2 start address Branch Box 1 oldest start address 1 05 1 06 A port address Start address 06 B port address Start address 1 07 C port address Start address 2 08 Ex2 Outdoor Branch 1 M S P series Indoor A C E Branch 2 M S P series Indoor A C E Outdoor address 51 1 1 Outdoor address Bra...

Страница 23: ...x 2 start address CITY MULTI series Indoor 1 address 1 06 1 07 A port address Start address 07 B port address Start address 1 08 C port address Start address 2 09 M S P series Indoor M S P series Indoor M S P series Indoor M S P series Indoor M S P series Indoor M S P series Indoor M S P series Indoor M S P series Indoor 01 A port 02 B port 03 C port 04 D port 05 E port CITY MULTI series Indoor 1 ...

Страница 24: ... and outdoor units check for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt M ohm tester to check that the resistance between the power supply terminals and ground is at least 1 MΩ Do not carry out this test on the control wiring low voltage circuit terminals Warning Do not use the air conditioner if...

Страница 25: ...farms or for commercial use by lay persons TÜRKÇE Aslı İngilizce dir Diğer dillerdeki sürümler aslının çevirisidir DİKKAT Soğutucu kaçağı boğulmaya neden olabilir EN378 1 uyarınca uygun havalandırma sağlayın Borular etrafına yalıtım yapıldığından emin olun Borulara doğrudan çıplak elle dokunulması yanıklara veya soğuk ısırıklarına neden olabilir Kazara yutmamak için pilleri kesinlikle hiçbir amaçl...

Страница 26: ...ly Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travellers Lane Hatfield Herts AL10 8XB England U K Polish Branch Krakowska 50 PL 32 083 Balic...

Отзывы: