7
A
(mm)
È
Liquid pipe
É
Gas pipe
PUMY-P112-140
ø9.52
ø15.88
B, C, D
(mm)
Ê
Total capacity of indoor units
È
Liquid pipe
É
Gas pipe
ø9.52
ø15.88
a, b, c, d, e, f
(mm)
Ë
Model number
È
Liquid pipe
É
Gas pipe
15, 20, 25, 32, 40, 50
ø6.35
ø12.7
63, 80, 100, 125, 140
ø9.52
ø15.88
Ì
Branch kit model
CMY-Y62-G-E
Í
4-Branching header
Î
8-Branching header
CMY-Y64-G-E
CMY-Y68-G-E
* When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor
unit, refer to the installation manual for the CONNECTION KIT when selecting the
pipe size and piping length.
4. Installing the refrigerant piping
A
H
B
C
L
ℓ
D
e
a
h
b
c
d
A
a
b
c
d
e
f
H
h
L
ℓ
A
: Outdoor Unit
B
: First Branch
C
: Indoor unit
D
: Cap
A+B+C+D+a+b+c+d+e
300 m
L = A+B+C+D+e
150 m
ℓ = B+C+D+e
30 m
H
50 m (Outdoor lower H
40 m)
h
15 m
A+a+b+c+d+e+f
300 m
L = A+f
150 m, ℓ = f
30 m
H
50 m (Outdoor lower H
40 m)
h
15 m
Fig. 4-1
4.2.2. Connection with Branch Box (Fig. 4-2)
Flared connections
• This unit has flared connections on each indoor unit and branch box and outdoor
unit sides.
• Remove the valve cover of the outdoor unit, then connect the pipe.
• Refrigerant pipes are used to connect the branch box and outdoor unit.
Fig. 4-2
L
I
h2
b2
b1
c1
a6
a5
a4
a3
a2
h3
h1
H
a1
a7 a8
Outdoor unit
Branch box
Indoor unit
Permissible
length
(one-way)
Total piping length
c1 + b1 + b2 + a1 + a2 + a3 + a4 + a5 + a6 + a7 + a8
150 m
Farthest piping length (L)
c1 + b2 + a8
80 m (b2
55 m, a8
25 m)
Piping length between outdoor unit and branch boxes
c1 + b1 + b2
55 m
Farthest branch box from the first joint (b2)
b2
30 m
Farthest piping length after branch box (l)
a8
25 m
Total piping length between branch boxes and indoor units
a1 + a2 + a3 + a4 + a5 + a6 + a7 + a8
95 m
Permissible
height differ-
ence
(one-way)
In indoor/outdoor section (H)*1
H
50 m (In case of outdoor unit is set higher than indoor unit)
H
40 m (In case of outdoor unit is set lower than indoor unit)
In branch box/indoor unit section (h1)
h1 + h2
15 m
In each branch unit (h2)
h2
15 m
In each indoor unit (h3)
h3
12 m
Number of bends
| c1 + b1 + a1 |, | c1 + b1 + a2 |, | c1 + b1 + a3 |, | c1 + b1 + a4 |, | c1 + b1 + a5 |, | c1 + b2 + a6 |,
| c1 + b2 + a7 |, | c1 + b2 + a8 |
15
*1 Branch box should be placed within the level between the outdoor unit and indoor units.
*1
4.2. Pipe length and height difference
4.2.1. Connection without Branch Box (Fig. 4-1)