2.4.3. Windy location installation

When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunction
may result.
The following shows two examples of precautions against strong winds.

1

Install an optional air guide if the unit is installed in a location where strong winds
from a typhoon, etc. may directly enter the air outlet. (Fig. 2-15)

A

Air guide

2

Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-16)

B

Wind direction

Fig. 2-15

B

Fig. 2-16

2. Installation location

3. Installing the outdoor unit

(mm)

• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during

operation. (Fig. 3-1)

<Foundation specifications>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

• Make sure that the length of the foundation bolt is within 30 mm of the bottom

surface of the base.

• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy locations.

Installing the outdoor unit

• Do not block the vent. If the vent is blocked, operation will be hindered and break-

down may result.

• In addition to the unit base, use the installation holes on the back of the unit to

attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 

×

 15

mm or less) and install on site.

 Warning:

• The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

Fig. 3-1

A

M10 (3/8") bolt

B

Base

C

As long as possible.

D

Vent

B

Max.

 30

A

C

D

4. Installing the refrigerant piping

4.1. Precautions for devices that use R410A refrigerant

• Refer to page 3 for precautions not included below on using air conditioners

with R410A refrigerant.

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.

 Warning:

When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

Indoor unit type

15-50

63-140

Liquid pipe

ø6.35 thickness 0.8 mm

ø9.52 thickness 0.8 mm

Gas pipe

ø12.7 thickness 0.8 mm

ø15.88 thickness 1.0 mm

• Do not use pipes thinner than those specified above.

600

600

Min. 360

175

175

Min. 10

950

25

330

370

A

Содержание PUMY-P-YHMA

Страница 1: ...ll unità interna prima di installare il condizionatore d aria MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙÂ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË ÂÛˆÙÂÚÈÎ ÌÔÓ ÚÔÙÔ ÂÁÎ Ù ÛÙ ÛÂÙÂ ÙË Ì...

Страница 2: ...n cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric sh...

Страница 3: ... refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Flare too...

Страница 4: ...tdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor unit installation You should note that indoor units that can be connected to this outdoor unit are the following models Indoor units with model numbers 15 140 PUMY P100 15 125 can be connected Refer to the table below for possible...

Страница 5: ...t rear sides and above only Fig 2 7 Do not install the optional air outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9 No more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides...

Страница 6: ... less and install on site Warning The unit must be securely installed on a structure that can sustain its weight If the unit is mounted on an unstable structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may fall down and cause...

Страница 7: ...usual pipe sealing is used refer to Table 1 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements A mm Å Liquid pipe ı Gas pipe PUMY P100 140 ø9 52 ø15 88 B C D mm Ç Total capacity of indoor units Å Liquid pipe ı Gas pipe ø9 52 ø15 88 a b c d e f mm Î Model number Å Liquid pipe ı Gas pipe 15 20 25 32 40 50 ø6 35 ø12 7 63 80 100 125 140 ø9 52 ø15 88 ...

Страница 8: ...sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1...

Страница 9: ...ork to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connected electrical parts will be burnt out 6 Use 2 core shield cable for transmission line If transmission lines of different systems are wired with ...

Страница 10: ...utomatically becomes 100 if it is set as 01 50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations among the multiple indoor units is done by the remote controller RC after the electrical power ...

Страница 11: ...is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 16 A 30 mA 0 1 sec or less 15 A 30 mA 0 1 sec or less 16 A 15 A 1 5 1 5 1 5 1 5 Indoor Unit Main Cable Minimum Wire Thickness mm2 Branch Breaker for Current Leak...

Страница 12: ...nifold valve and put the cap back onto each stop valve Note 1 Never carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant ex ceeds the amount of charge less refrigerant will cause an extreme pres sure rise and may result in an accident 2 Do not continue...

Страница 13: ...2006 95 EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U713H04 The product at hand is based on the following EU regulations ...

Отзывы: