8
3-2. STANDARD OPERATION DATA
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
T
otal
Capacity
W
7,500 9,000
Input
kW
3.04
2.15
Electrical circuit
Outdoor unit
PUHZ-W85VHA2
Phase, Hz
1, 50
Voltage
V
230
Current
A
13.15
9.38
Refrigerant circuit
Discharge pressure
MPa
2.81
2.16
Suction pressure
MPa
0.73
0.64
Discharge temperature
ºC
80
65
Condensing temperature
ºC
46
37
Suction temperature
ºC
3
-1
W
ater
conditions
Flow volume
L/min
21.5
25.8
Outlet water temperature
ºC
7
35
Outdoor
conditions
Intake air
temperature
D.B.
ºC
35
7
W.B.
ºC
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm²)
We confirm that our units are tested based on EN 14511.