45
OCH681
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Capacity setting display
Displayed as an outdoor capacity code.
Code
display
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor unit setting information
Plate HEX liquid pipe temperature (TH6)
−40 to 90
Code
display
:
−40 to 90
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
Return water temperature
0 to 100
Capacity
W85
W112
Code
14
20
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P
1 : Cooling only
0 :
Single phase 2 : 3 phase
Setting details
Defrosting switch
Display details
0 : Normal
1 : For high humidity
(Example) When heat pump, 3 phase and
defrosting (normal) are set up, “20” is
displayed.
1
ON
2 3 4 5 6
Condensing temperature (T63HS)
−39 to 88
−39 to 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
:
0 to 100
The black square (
■
) indicates a switch position.
1
ON
2 3 4 5 6
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Flow water temperature
0 to 100
Water inlet temperature (TH34)
0 to 100
0 to 100
:
:
0 to 100
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
Outdoor outside temperature (TH7)
−40 to 90
−40 to 90
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)