12
OCH681
PUHZ-W112VAA.UK PUHZ-W112YAA.UK
REV/V
CHECK/V(H)
H/P SW
TH4
COMP
CHECK/V(L)
Strainer2
(#100)
Strainer1
LEV-A
LEV-B
Strainer3
(#100)
(#100)
(#100)
Strainer4
Rec
CHECK/V(C)
Plate HEX
Water OUT
Water IN
Water IN
Water OUT
TH8
TH3
P/B
TH7
Heat exchanger
P -SENSOR
Strainer5
(#100)
L/P SW
D
is
tri
bu
te
r
TH6
TH33
TH34
Refrigerant flow in cooling
Refrigerant flow in heating
Symbol
Parts name
Detail
COMP
Compressor
DC inverter scroll compressor (Mitsubishi Electric Corporation)
H/P SW
High pressure switch (63H)
For protection (OFF: 4.15MPa)
L/P SW
Low pressure switch (63L)
For protection (OFF: -0.03MPa)
REV/V
Reversing (4-way) valve (21S4)
Change the refrigerant circuit (Heating / Cooling) and for
Defrosting
CHECK/V
Charge plug
High pressure/Low pressure/For production test use
P-SENSOR
Pressure sensor (63HS)
For calculation of the condensing temperature from high
pressure
LEV-A
Linear expansion valve -A
Heating: Secondary LEV Cooling: Primary LEV
LEV-B
Linear expansion valve -B
Heating: Primary LEV Cooling: Secondary LEV
TH3
Liquid temperature thermistor
Heating: Evaporating temperature
Cooling: Sub cool liquid temperature
TH4
Discharge temperature thermistor
For LEV control and for compressor protection
TH6
Plate HEX liquid temperature thermistor
Heating: Sub cool liquid temperature
Cooling: Evaporating temperature
TH7
Ambient temperature thermistor
For fan control and for compressor frequency control
TH8
Heat sink temperature thermistor
For power board protection
TH33
Comp. surface temperature thermistor For protection
TH34
Inlet water temperature thermistor
For freeze protection and for compressor frequency control
Rec
Receiver
For accumulation of refrigerant
P/B
Power circuit board
For flow temp. controller
Plate HEX
Plate Heat Exchanger
MWA1-44DM
TH1, THW1
Outlet water temperature thermistor
For flow temp. controller
<Reference>
System example
Содержание PUHZ-W112VAA 11.2kW Mono