13
Total
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Representative matching
SHF
BF
W
kW
Mode
Capacity
Input
Phase , Hz
Volts
Amperes
Outdoor unit
Phase , Hz
Volts
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
MPa
MPa
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
PLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
PLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
Cooling
10,000
3.02
Heating
11,200
3.02
Cooling
12,500
3.87
Heating
14,000
3.88
Cooling
14,000
4.65
Heating
16,000
4.69
12.53
2.55
0.94
63
44
11
5
27
19
13.0
35
24
0.78
0.04
12.39
2.46
0.70
70
42
3
5
20
15
42.5
7
6
—
—
15.53
2.72
0.88
69
46
9
5
27
19
12.2
35
24
0.74
0.05
15.98
2.73
0.66
76
47
2
5
20
15
45.5
7
6
—
—
19.65
2.86
0.81
76
48
8
5
27
19
11.2
35
24
0.71
0.05
19.92
2.90
0.64
83
50
1
5
20
15
49.6
7
6
—
—
1 , 50
230
0.92
1 , 50
230
1 , 50
230
0.92
1 , 50
230
1 , 50
230
0.92
1 , 50
230
PUHZ-RP100VHA2
PUHZ-RP125VHA2
PUHZ-RP140VHA2
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/
f
f
)
OC374A--1.qxp 06.7.26 5:07 PM Page 13