Error Code
Abnormal points and detection method
Case
Judgment and action
U8
(4400)
Outdoor fan motor
Abnormal if rotational frequency of the fan
motor is not detected during DC fan motor
operation.
Fan motor rotational frequency is abnor-
mal if;
• 100 rpm or below detected continuously
for 15 seconds at 20
:
or more outside
air temperature.
• 50 rpm or below or 1500 rpm or more
detected continuously for 1 minute.
1
Failure in the operation of
the DC fan motor
2
Failure in the outdoor circuit
controller
board
1
Check or replace the DC fan motor.
2
Check the voltage of the outdoor circuit
controller board during operation.
3
Replace the outdoor circuit controller
board. (when the failure is still indicated
even after performing the action
1
above.)
U9
(4220)
Overvoltage or voltage shortage and
synchronous signal to main circuit
Abnormal if any of followings are detected
during compressor operation;
• Decrease of DC bus voltage to 310V
(RP35-140V only)
•
Instantaneous decrease of DC bus volt-
age
RP35-140V : 200V
RP100-140Y : 350V
•
Increase of DC bus voltage to
RP35-71V : 420V
RP100-140V : 400V
RP100-140Y : 760V
• Decrease of input current of outdoor unit
to 0.5A only if operation frequency is
more than or equal to 40Hz or compres-
sor current is more than or equal to 5A.
1
Decrease of power supply volt-
age
2
Disconnection of compressor
wiring
3
Defective 52C
(RP100-140VHA2)
4
Defective noise filter circuit
board
(RP100-140VHA2
1
,100VHA3)
5
Disconnection or loose con-
nection of CN52C (RP35-
71V, RP100-140VHA2
1
,
RP100VHA3)
6
Defective PFC module of out-
door power board (RP35-71V)
7
Defective ACT module
(RP100-140V)
8
Defective ACT module drive
circuit of outdoor power circuit
board (RP100-140V)
9
Disconnection or loose connec-
tion of CNAF (RP100-140V)
0
Defective outdoor converter cir-
cuit board (RP100-140Y)
1
Defective 52C drive circuit of
outdoor controller circuit board
(RP35-140VHA2)
2
Disconnection or loose
connection of CN5 on the
outdoor power circuit board
3
Defective 52C drive circuit of
outdoor power circuit board
(RP100-140Y)
4
Disconnection or loose
connection of CN2 on the
outdoor power circuit board
1
Check the facility of power supply.
2
Correct the wiring (U
•
V
•
W phase) to com-
pressor. Refer to 11-9 (Outdoor power circuit
board).
3
Replace 52C.
4
Replace noise filter circuit board.
(RP100-140VHA2
1
, RP100VHA3)
5
Check CN52C wiring.
6
Replace outdoor power circuit board.
(RP35-71V)
7
Replace ACT module. (RP100-140V)
8
Replace outdoor power circuit board.
(RP100-140V)
9
Check CNAF wiring. (RP100-140V)
0
Replace outdoor converter circuit board.
(RP100-140Y)
1
Replace outdoor controller circuit board.
(RP35-140VHA2)
2
Check CN5 wiring on the outdoor power cir-
cuit board.
Refer to 11-9.
3
Replace outdoor power circuit board.
(RP100-140Y)
4
Check CN2 wiring on the outdoor power cir-
cuit board. Refer to 11-9.
UF
(4100)
Compressor overcurrent interruption
(When compressor locked)
Abnormal if overcurrent of DC bus or
compressor is detected within 30 seconds
after compressor starts operating.
1
Stop valve is closed.
2
Decrease of power supply
voltage
3
Looseness, disconnection or
converse of compressor wiring
connection
4
Defective compressor
5
Defective outdoor power board
1
Open stop valve.
2
Check facility of power supply.
3
Correct the wiring (U
•
V
•
W phase) to
compressor.
Refer to 11-9 (Outdoor power circuit board).
4
Check compressor.
Refer to 11-6.
5
Replace outdoor power circuit board.
Ud
(1504)
Over heat protection
Abnormal if outdoor pipe thermistor (TH3)
detects 70
:
or more during compressor
operation.
1
Defective outdoor fan (fan
motor) or short cycle of out-
door unit during coling opera-
tion
2
Defective outdoor pipe ther-
mistor (TH3)
3
Defective outdoor controller
board
1
Check outdoor unit air passage.
23
Turn the power off and on again to check
the error code. If U4 is displayed, follow the
U4 processing direction.