•PUHY-P250YJM-A(-BS)
49
10
20
30
40
50
60
70
80
90
63
125
250
500
1k
2k
4k
8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octa
v
e
band sound le
v
el (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low
50/60Hz
5. Sound Pressure Levels
Measurement
location
1m
1m
•PUHY-P500YSJM-A(-BS)
Measurement
location
1m
1m
10
20
30
40
50
60
70
80
90
63
125
250
500
1k
2k
4k
8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octa
v
e
band sound le
v
el (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low
50/60Hz
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
60.0
63.0
61.0
55.0
52.0
47.5
42.5
36.5
58.0
Low noise mode 50/60Hz
58.0
54.0
44.0
39.5
37.0
33.0
31.5
25.0
44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
63.0
66.0
64.0
58.0
55.0
50.5
45.5
39.5
61.0
Low noise mode 50/60Hz
61.0
57.0
47.0
42.5
40.0
36.0
34.5
28.0
47.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Содержание PUHY-P-YSJM-A
Страница 1: ...DATA BOOK AIR CONDITIONING SYSTEMS MODEL PUHY P Y S JM A PFAV P VM E F ...
Страница 2: ......
Страница 94: ...91 2 Sample control wiring Different refrigerant group operation Refer to the section 3 2 1 Address Setting ...
Страница 97: ...94 3 Emergency Operation Mode a a a b c d a c ...
Страница 98: ...95 b a a a b a b b b ...
Страница 100: ...97 ...
Страница 101: ...98 ...
Страница 103: ......