SP007-27
8
CAPACITY CORRECTION FACTORS FOR VARIOUS
PIPE LENGTHS
MODEL
Refrigerant piping length (one way)
PUG/H18
PUG/H24
PUG/H30
PUG/H36
PUG/H42
1.0
1.0
1.0
1.0
1.0
25ft
0.992
0.981
0.981
0.981
0.975
40ft
0.983
0.968
0.968
0.968
0.955
55ft
0.978
0.952
0.952
0.952
0.935
70ft
0.966
0.940
0.940
0.940
0.918
85ft
0.959
0.925
0.925
0.925
0.900
100ft
0.950
0.913
0.913
0.913
0.884
115ft
0.945
0.900
0.900
0.900
0.869
130ft
0.886
0.886
0.886
0.855
150ft
1) COOLING CAPACITY
Models
Refrigerant piping length (one way)
PUG/H18
PUG/H24
PUG/H30
PUG/H36
PUG/H42
1.00
1.00
1.00
1.00
1.00
Less than 100ft
0.995
0.995
0.995
0.995
0.995
100~130ft
0.990
0.990
0.990
0.990
0.990
130~150ft
2) HEATING CAPACITY