13. INSTALLATION
13-1. PQRY-P-T(S)LMU/Y(S)LMU’s Installation
13-2. Installation Space
1. No direct thermal radiation to the unit.
2. No possibility of annoying the neighbors by the sound of the unit.
Valves and refrigerant flow on the Heat source unit may generate noise.
3. Avoid the sites where strong winds blow.
4. With strength to bear the weight of the unit.
5. Drain flow from the unit is cared at heating mode.
6. Enough space for installation and service as shown at 13-2.
7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.
8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.
Unit: mm (in.)
control box
The space for
replacement
(front side)
Service space
(front side)
Service space
Top view
control box
The space for
replacement
600(23-5/8)
450(17-3/4)
600(23-5/8)
450(17-3/4)
350(13-13/16)
880(34-11/16)
In case of a single unit installation, 23-11/16 in. (600mm) or more of clearance space in the front of the unit makes for easier access
when servicing the unit.