WR2-108
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
© 2017 Mitsubishi Electric US, Inc.
PQRY-P72TLMU/YLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.15 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bent on the piping) [m]
PQRY-P96TLMU/YLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.38 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bent on the piping) [m]
PQRY-P120TLMU/YLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.54 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 x number of bent on the piping) [m]
PQRY-P144, 168, 192, 216, 240T(S)LMU/Y(S)LMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bent on the piping) [m]
PQRY-P288, 312TSLMU/YSLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (2.29 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bent on the piping) [m]
PQRY-P336TSLMU/YSLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (2.70 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bent on the piping) [m]
8-9-3. How to Obtain the Equivalent Piping Length
8. CAPACITY TABLES