1 - 21
1. SPECIFICATIONS
PEFY-VMA
MEE15K052
Model
PEFY-WP50VMA-E
Power source
1-phase 220-230-240 V 50/
60 Hz
Cooling capacity
*1 kW
5.6
(Nominal)
*1 kcal/h
4,800
*1 BTU/h
19,100
*2 Power input
kW
0.14
*2 Current input
A
1.15
Heating capacity
*3 kW
6.3
(Nominal)
*3 kcal/h
5,400
*3 BTU/h
21,500
*2 Power input
kW
0.12
*2 Current input
A
1.04
External finish
Galvanized steel plate
External dimension HxWxD
mm
250 x 1,100 x 732
in.
9-7/8 x 43-5/16 x 28-7/8
Net weight
kg (lbs)
31 (69)
Heat exchanger
Cross fin (Aluminum fin and
copper tube)
Water Volume
L
1.8
FAN
Type x Quantity
Sirocco fan x 2
*4 External static press.
Pa
<35> - 50 - <70> - <100> -
<150>
mmH
2
O
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
Motor Type
DC motor
Motor output
kW
0.121
Driving mechanism
Direct-driven by motor
Air flow rate
(Low-Mid-High)
m
3
/min
14.5 - 18.0 - 21.0
L/s
242 - 300 - 350
cfm
512 - 636 - 742
Sound pressure level (measured in anechoic room)
(Low-Mid-High)
*2 dB <A>
26-29-34
Insulation material
EPS, Polyethylene foam,
Urethane foam
Air filter
PP honeycomb fabric.
Protection device
Fuse
Refrigerant control device
-
Connectable outdoor unit/HBC controller
CITY MULTI YLM series/
CMB-WP-V-GA1, CMB-WP-
V-GB1
Diameter of water pipe
Inlet
in.
Rc 3/4 screw
*5 *6 Outlet
in.
Rc 3/4 screw
Field drain pipe size
mm (in.)
O.D.32 (1-1/4)
Drawing
External
KD94L918X01
Wiring
KD94L919X01
Refrigerant cycle
-
Standard attachment
Document
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for water pipe,
Washer, Drain hose, Tie
band
Optional parts
Filter box
PAC-KE93TB-E
Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions
Indoor: 27°CD.B./19°CW.B. (81°CD.B./66°CW.B.), Outdoor: 35°CD.B. (95°CD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20°CD.B. (68°CD.B.), Outdoor: 7°CD.B./6°CW.B. (45°CD.B./43°CW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Be sure to install a valve on the water outlet.
6.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters.
7.Group units that operate on 1 branch.
kcal/h =kW x 860
BTU/h =kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg / 0.4536
*Above specification data is
subject to rounding variation.
0000003898.BOOK 21 ページ 2016年1月13日 水曜日 午前10時30分
Содержание PLFY-WP VBM-E
Страница 3: ...MEE15K052 ...
Страница 5: ...1 2 MEE15K052 ...
Страница 39: ...1 36 MEE15K052 ...
Страница 42: ...1 39 PLFY VBM MEE15K052 2 EXTERNAL DIMENSIONS 2 EXTERNAL DIMENSIONS PLFY WP32 40 50VBM E Unit mm ...
Страница 44: ...1 41 PLFY VBM MEE15K052 4 ELECTRICAL WIRING DIAGRAMS 4 ELECTRICAL WIRING DIAGRAMS PLFY WP32 40 50VBM E ...
Страница 63: ...1 60 MEE15K052 ...
Страница 79: ...1 76 MEE15K052 ...
Страница 89: ...1 86 MEE15K052 ...
Страница 90: ...2 1 HYBRID CITY MULTI 2 OUTDOOR HEAT SOURCE UNITS MEE15K052 YLM R2 SERIES 2 3 YLM WR2 SERIES 2 37 ...
Страница 91: ...2 2 MEE15K052 ...
Страница 125: ...2 36 MEE15K052 ...
Страница 155: ...3 2 MEE15K052 ...
Страница 169: ...3 16 MEE15K052 ...
Страница 183: ...3 30 MEE15K052 ...