![Mitsubishi Electric PLFY-P32VKM Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/mitsubishi-electric/plfy-p32vkm/plfy-p32vkm_technical-and-service-manual_1811121017.webp)
17
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
5. Removing the room temperature thermistor
(1) Remove the fan guard.
(2) Remove the electrical box cover
(3) Remove the holder and the room temperature thermistor
by pulling the catch.
(4) Disconnect the red connector, CN20, on the indoor
controller board.
6. Removing the liquid pipe thermistor
(1) Remove the fan guard.
(2) Remove the electrical box cover.
(3) Remove the electrical box.
(4) Remove the turbo fan.
(5) Remove the screw of the service panel.
(6) Remove the service panel.
(7) Remove the liquid pipe thermistor(TH22) from the holder
attached to the copper pipe.
(8) Disconnect the 2-pin white connector.
7. Removing the panel
(1) Open the intake grille.
(2) Disconnect the connector the vane motor.
(3) Remove 4 screws of the panel.
(4) Pulling the temporary handing hook, remove the panel.
8. Removing the drain pan
(1) Remove the panel.
(2) Remove the fan guard.
(3) Remove the rubber bushing.
(4) Drain the remaining water in the drain pan.
(5) Remove the electrical box cover.
(6) Remove the electrical box.
(7) Remove the screw of the V.A. cover, and remove the V.A.
cover.
(8) Remove each screw of the corner supports 1,2, and 3,
and remove the corner supports 1,2 and 3.
(9) Pull out the drain pan.
w
Pull the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Photo 8
Photo 7
Photo 6
Photo 5
Indoor controller board
Room
temperature
thermistor
Mounting hole
Corner
support 1
Corner
support 3
VA cover
Rubber
bush
Corner
support 2
Screws
screws
screws
Panel
Fan guard
Temporary hanging hook
Temporary hanging hook
Liquid pipe thermistor(TH22)