![Mitsubishi Electric PLFY-P32VKM Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/mitsubishi-electric/plfy-p32vkm/plfy-p32vkm_technical-and-service-manual_1811121011.webp)
11
TROUBLE SHOOTING
7
7-1. How to check the parts PLFY-P•VKM.UK
Parts name
Check points
Trans
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10°W~30°C)
Disconnect the connector then measure the resistance using a tester.
Refer to the next page for a detail.
Disconnect the connector and measure the resistance using a tester.
Measure the resistance between the terminals using a tester.
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20°C~30°C)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20°C~30°C)
Measure the resistance between the terminals using a tester.
Vane motor
Fan motor
Linear expansion
valve
Drain-up
mechanism
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperature
thermistor (TH21)
Liquid pipe thermistor
(TH22)
Gas pipe thermistor
(TH23)
1
2
3
1
2
3
CNT
T
CN3T
Red
Blue
Blue
White
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
1
2
Gray
Gray
1
2
3
4
5
Normal
4.3k
Ω
~9.6k
Ω
Abnormal
Open or short
CNT(1)~(3)
CN3T(1)~(3)
Abnormal
Open or short
Normal
Approx. 45
Ω
Approx. 1
Ω
(1)-(3)
(4)-(5)
Abnormal
Open or short
Normal
82
Ω
4.3k
Ω
~9.6k
Ω
Abnormal
Open or short
Normal
150k
Ω
i
10%
(1)-(5)
White-Red
(2)-(6)
Yellow-Blown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
Abnormal
Open or short
Normal
PLFY-P·VKM.UK
P32, P40, P50, P63
136.2k
Ω
197.5k
Ω
Red-Black
White-Black
Motor terminal
or
Relay connector
Normal
Abnormal
Approx. 14k
Ω
Open or short
Normal
Abnormal
327
Ω
Open or short
Orange
Red
White
Blue
Brown
Yellow
3
6
1
5
4
2
M