11
11
3-1. SPECIFICATIONS
3
SPECIFICATIONS
Service Ref.
PLFY-P15VFM-E1.TH PLFY-P20VFM-E1.TH PLFY-P25VFM-E1.TH PLFY-P32VFM-E1.TH PLFY-P40VFM-E1.TH PLFY-P50VFM-E1.TH
power source
single phase, 220-230-240 V, 50 Hz / 220 V, 60 Hz
cooling capacity
*1
kW
1.7
2.2
2.8
3.6
4.5
5.6
*1 kcal/h
1,450
1,900
2,400
3,100
3,900
4,800
*1 BTU/h
5,800
7,500
9,600
12,300
15,400
19,100
*2
kcal/h
1,500
2,000
2,500
3,150
4,000
5,000
Power input kW
0.02
0.02
0.02
0.02
0.03
0.04
Current input A
0.19
0.21
0.22
0.23
0.28
0.40
Heating capacity
*3
kW
1.9
2.5
3.2
4.0
5.0
6.3
*3
kcal/h
1,600
2,200
2,800
3,400
4,300
5,400
*3
BTU/h
6,500
8,500
10,900
13,600
17,100
21,500
Power input kW
0.02
0.02
0.02
0.02
0.03
0.04
Current input A
0.14
0.16
0.17
0.18
0.23
0.35
External finish
Galvanized steel sheet
External dimension
H × W × D
mm
208 × 570 × 570
8-1/4" × 22-1/2" × 22-1/2"
in
Net wight
kg (lb)
14 (31)
14 (31)
14 (31)
15 (33)
15 (33)
15 (33)
Decoration
panel
model
SLP-2FA(L)(E)
External finish
Munsell 1.0Y 9.2/0.2
Dimension
H × W × D
mm
10 × 625 × 625
3/8" × 24-5/8" × 24-5/8"
in
Net weight kg (lb)
3(7)
Heat exchanger
Cross fin (Aluminum fin and copper tube)
FAN
Type
Turbo fan × 1
External pressure
0 Pa (0 mmH
2
O)
Motor type
DC motor
Motor output kW
0.05
Driving mechanism
Direct driven
Airflow
rate
K
/min
6.5-7.5-8.0
6.5-7.5-8.5
6.5-8.0-9.0
7.0-8.0-9.5
7.5-9.0-11.0
9.0-11.0-13.0
L/s
108-125-133
108-125-142
108-133-150
117-133-158
125-150-183
150-183-217
cfm
230-265-282
230-265-300
230-282-318
247-282-335
265-318-388
318-388-459
Noise level
(Low-Mid-High)
(measured in anechoic room)
dB <A>
26-28-30
26-29-31
26-30-33
26-30-34
28-33-39
33-39-43
Insulation material
PS
Air filter
PP honeycomb fabric (long life type)
Protection device
Fuse
Refrigerant control device
LEV
Connectable outdoor unit
R410A CITY MULTI
Diameter
of
refrigeant
pipe
Liquid
mm (in)
ø6.35 (ø1/4") Flare
Gas
mm (in)
ø12.7 (ø1/2") Flare
Field drain pipe size mm (in)
O.D. 32 mm (1-1/4") (PVC pipe VP-25 connectable)
Standard attachment
Installation manual, Instruction book
Remark Optional parts
Decoration panel : SLP-2FA, SLP-2FAE, SLP-2FAL, SLP-2FALE, SLP-2FALM, or SLP-2FALME
*PLFY-P-VFM-E1 should be used together with decoration panel.
Installation
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
*1 Nominal cooling condition
Indoor :
Outdoor :
Pipe length :
Level difference :
27
˚CDB/19˚CWB (81˚FDB/66˚FWB)
35
˚CDB (95˚FDB)
7.5
m (24-9/16 ft)
0
m (0 ft)
*2 Nominal cooling condition
27
˚CDB/19.5˚CWB (81˚FDB/67˚FWB)
35
˚CDB (95˚FDB)
5
m (16-3/8 ft)
0
m (0 ft)
*3 Nominal heating condition
20
˚CDB (68˚FDB)
7˚CDB/6˚CWB (45˚FDB/43˚FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
*1 and *3 are subject to JIS B8615-1.
2.
Due to continuing improvement, above specification may be subject to change without notice.
1. Nominal conditions
Notes:
Unit converter
kcal= kW × 860
BTU/h =3,412
cfm =
K
/min ×
35.31
lb = kg/0.4536
OCH617