3-2. Electrical parts specifications
Parts name
Model
Symbol
TH21
TH22
TH23
FUSE
MF
C1
MV
DP
DS
LEV
H2
TB2
TB5
Resistance 0
:
/15k
"
, 10
:
/9.6k
"
, 20
:
/6.3k
"
, 25
:
/5.4k
"
, 30
:
/4.3k
"
, 40
:
/3.0k
"
Resistance 0
:
/15k
"
, 10
:
/9.6k
"
, 20
:
/6.3k
"
, 25
:
/5.4k
"
, 30
:
/4.3k
"
, 40
:
/3.0k
"
Resistance 0
:
/15k
"
, 10
:
/9.6k
"
, 20
:
/6.3k
"
, 25
:
/5.4k
"
, 30
:
/4.3k
"
, 40
:
/3.0k
"
250V 6.3A
240V 21.8W
(L, N,
;
) 330V 30A
(M1, M2, S) 250V 30A
Liquid pipe thermistor
Gas pipe thermistor
Fan motor capacitor
Vane motor
Drain-up mechanism
Drain sensor
Linear expansion valve
PLFY-P80VAM.UK
PLFY-P100VAM.UK
PLFY-P125VAM.UK
Room temperature
thermistor
Fuse
(Indoor controller board)
Fan motor
(with inner-thermostat)
Inner-thermostat
(Fan motor)
Electric heater
(Condensation proof)
Power supply terminal
block
Transmission terminal
block
6-pole OUTPUT 120W
D176P120MS
6-pole OUTPUT 70W
D17B6P70MS
MSBPC20M04
DC12V 300
"
/phase
PLD-12230ME-1
INPUT 12/10.8W 24
R
/Hr
Thermistor resistance 0
:
/6k
"
, 10
:
/3.9k
"
, 20
:
/2.6k
"
, 25
:
/2.2k
"
, 30
:
/1.8k
"
, 40
:
/1.3k
"
DC12V Stepping motor drive / Port dimension
[
5.2 (0~2000pulse)
EDM-804ME
OFF 130
:
i
5
:
ON 90
:
i
20
:
3.5
+
440V
7.0
+
440V
4
4-WAY AIR FLOW SYSTEM
4-1. Placement of the air outlets
For this grille, the discharge direction comes in 11 patterns.
Also, by setting the dip switches (SWA and SWB) on the indoor board to the appropriate settings, you can adjust the air flow
and speed. Select the settings from the Table below according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
Discharge direction
pattern
4-direction
<Table 1>
3-direction
2-direction
Note :
For 3 and 2-directional,
please use the air outlet
shutter plate (option).
Pattern 1
Factory setting
Pattern 4
One air outlet
fully closed
Pattern 6
Two air outlets
fully closed