8

6.  Electrical work

6..  Remote controller

6..1.  For wired remote controller

1)  Two wired remote controllers setting

If two wired remote controllers are connected, set one to “Main” and the other to 

“Sub”. For setting procedures, refer to “Function selection of remote controller” in 

the operation manual for the indoor unit.

6...  For IR wireless remote controller

1)  Setting (Fig. 6-3)

  Insert batteries.

  Press the SET button with something sharp at the end.

 

MODEL SELECT

blinks and Model No. is lighted.

  Press the temp 

buttons to set the Model No.

If you mistook the operation, press the ON/OFF 

 button and operate again 

from procedure  .

  Press the SET button with something sharp at the end.

 

MODEL SELECT

and Model No. are lighted for three seconds, then turned off.

Indoor

Outdoor

 Model No.

PLA

heat pump models

001

cooling only models

033

)Automatic fan speed setting (For IR wireless remote controller) (Fig. 6-4)

It is necessary to set for IR wireless remote controller only when automatic fan 

speed is not set at default setting.

It is not necessary  to set for wired remote controller with automatic fan speed at 

default setting.

 Press the SET button with something sharp at the end.

Operate when display of remote controller is off.
 

MODEL SELECT

 blinks and Model No. is lighted  .

 Press the AUTO STOP 

 button.

 blinks and setting No. is lighted  .

(Setting No.01: without automatic fan speed )

 Press the temp.

 buttons to set the setting No.02.

    (Setting No.02:with automatic fan speed ) 

If you mistook the operation, press the ON/OFF 

 button and operate again 

from procedure  .

 Press the SET button with something sharp at the end.

MODEL SELECT

 and Model No. are lighted for 3 seconds, then turned off.

Fig. 6-3

Fig. 6-4

3)  Assigning a IR wireless remote controller to each unit (Fig. 6-5)

Each unit can be operated only by the assigned remote controller.

Make sure each pair of an indoor unit PC board and a IR wireless remote controller 

is assigned to the same pair No.

4)  IR wireless remote controller pair number setting operation (Fig. 6-5)

  Press the SET button with something sharp at the end.

  Start  this  operation  from  the  status  of  IR  wireless  remote  controller  display 

turned off.  

MODEL SELECT

 blinks and Model No. is lighted.

  Press the 

min

 button twice continuously.

  Pair No. “0” blinks.

  Press the temp 

 buttons to set the pair number you want to set.

If you mistook the operation, press the ON/OFF 

 button and operate again 

from procedure 2.

  Press the SET button with something sharp at the end.

  Set pair number is lighted for three seconds then turned off.

 

 

 Pair No. of IR wireless remote controller

Indoor PC board

0

Factory setting

1

Cut J41

2

Cut J42

3-9

Cut J41, J42

Fig. 6-5

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

MODEL SELECT

*1. Max. 50 m, 165 ft
*2. The 10m, 30 ft wire is attached in the wired remote controller accessory. Max. 500 m, 1500ft

*3. The figures are NOT always against the ground.

  S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.

 

.  Use copper supply wires.

 

3.  Use wires rated 300V or more for the power supply cables and the indoor unit/outdoor unit connecting cables.

 

4.  Install an earth longer than other cables.

Indoor unit model

PLA-A12, 18, 24, 30

PLA-A36, 42

Minimum circuit ampacity

1A

2A

Maximum rating of overcurrent protective device

15A

15A

Wir

ing

Wire No

. × siz

e

Indoor unit-Outdoor unit

*1

3 × AWG16 (polar)

3 × AWG16 (polar)

Indoor unit earth

1 × Min. AWG16

1 × Min. AWG16

Wired remote contoroller-Indoor unit

*2

2 × AWG22 (Non-polar)

2 × AWG22 (Non-polar)

Circuit

rating

Indoor unit-Outdoor unit S1-S2

*3

AC 208/230 V

AC 208/230 V

Indoor unit-Outdoor unit S2-S3

*3

DC24 V

DC24 V

Wired remote controller-Indoor unit

*3

DC12 V

DC12 V

01_RG79D307K02_EN.indd   8

2010/09/01   11:03:26

Содержание PLA-A-BA4 Series

Страница 1: ...A4 English INSTALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER 01_RG79D307K02_EN indd 1 2010 09 01 11 03 22 ...

Страница 2: ...e gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explosion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wate...

Страница 3: ... The method for using the template and the gauge is shown Before using check the dimensions of template and gauge because they change due to fluctuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance betw...

Страница 4: ...prior to installation of the decorative cover or when applying ceiling materials 3 7 Confirming the position of main unit and tightening the suspension bolts Fig 3 8 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that th...

Страница 5: ...n pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use two wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully B Flare nut tightening tor...

Страница 6: ...ised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 mm 1 1 4 inch PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 mm 1 1 2 inch PVC TUBE for grouped piping 9 mm 23 64 inch or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 850 mm 33 7 16 inch 1 Connect the drain socket supplied with the unit to the drain po...

Страница 7: ...d 6 1 1 Indoor unit power supplied from outdoor unit The following connection patterns are available The outdoor unit power supply patterns vary on models 1 System S1 S2 L N 1 2 S1 S2 S3 S3 A B C D E F G I H CN105 RED S1 S2 L N 1 2 S1 S2 S3 1 2 S1 S2 S3 S3 A B C D E F G G E Affix label A that is included with the manuals near each wiring diagram for the indoor and outdoor units A Outdoor unit powe...

Страница 8: ...ir of an indoor unit PC board and a IR wireless remote controller is assigned to the same pair No 4 IR wireless remote controller pair number setting operation Fig 6 5 Press the SET button with something sharp at the end Start this operation from the status of IR wireless remote controller display turned off MODELSELECT blinks and Model No is lighted Press the min button twice continuously Pair No...

Страница 9: ...n from the status of IR wireless remote controller display turned off CHECK is lighted and 00 blinks Press the temp button once to set 50 Direct the IR wireless remote control ler toward the receiver of the indoor unit and press the h button Setting the unit number Press the temp buttons and to set the unit number 00 Direct the IR wireless remote controller toward the receiver of the indoor unit a...

Страница 10: ...t equipped with outdoor air intake 2 Supported indoor unit is equipped with outdoor air intake 3 Power voltage 230 V 04 104 1 208 V 2 Select unit numbers 01 to 03 or all units AL wired remote controller 07 wireless remote controller Mode Settings Mode No Setting no Initial setting setting Wired remote controller RF thermostat Filter sign 100Hr 07 107 1 2500Hr 2 No filter sign indicator 3 Fan speed...

Страница 11: ...ontrol system error memory error etc No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc IR wireless remote controller Wired remote controller RF thermostat Symptom Remark Beeper sounds OPERATION INDICATOR lamp blinks Number of times Check ...

Страница 12: ...er power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 GR Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and out...

Страница 13: ...er panel Slide the corner panel as indicated by the arrow to remove the corner panel Fig 9 3 Fig 9 4 Intake grille Grille Intake grille levers Grille hook Hole for the grille s hook Corner panel Screw Detail 9 3 Selection of the air outlets For this grille the discharge direction is available in 11 patterns Also by setting the wired remote controller to the appropriate settings you can adjust the ...

Страница 14: ...PLP 42BALM the connector of wireless sensor cable is also connected to connecor CN90 on indoor controller board The lead wire of grille is passed through the catch of bell mouth of the unit perfectly The remaining lead wire is tied with clamp of the unit and put the cover of the unit again with 2 screws Note Do not put the remaining lead wire in electrical branch box of the unit 9 5 Locking the up...

Страница 15: ...on procedures 10 Easy maintenance function For PUZ A PUY A application only Only for wired remote cpontroller By using the maintenance mode you can display many types of maintenance data on the wired remote controller such as the heat exchanger temperature and com pressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not ...

Страница 16: ...handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan RG79D307K02 01_RG79D307K02_EN indd 16 2010 09 01 11 03 34 ...

Отзывы: