background image

15

(1) Press the 

TEST

 button for three seconds to

activate the maintenance mode.

(2) Press the TEMP.

 buttons to set the refrigerant address.

MAINTENANCE

(3) Select the data you want to display.

MENU

ON/OFF

Compressor
information

COMP ON

x10 HOURS

COMP ON

x100 TIMES

COMP ON

CURRENT (A)

Cumulative
operation time

ON/OFF
number

Operation
current

Display 

Display 

Display 

OUTDOOR UNIT

H•EXC. TEMP

OUTDOOR UNIT

OUTLET TEMP

OUTDOOR UNIT

OUTDOOR TEMP

Heat exchanger
temperature

Comp discharge
temperature

Outdoor ambient
temperature

Display 

Outdoor unit
information

INDOOR UNIT

INLET TEMP

INDOOR UNIT

H•EXC. TEMP

INDOOR UNIT

FILTER USE H

Indoor room
temperature

Heat exchanger
temperature

Filter operation
time

Display 

Indoor unit
information

* The filter operation time displayed is the number of hours the filter has been

used since the filter reset was performed.

(4) Press the 

FILTER

 button.

(5) The data is displayed in  .

(Airflow temperature display example)

Blinking

Waiting for
response

Approx.

10 sec.

* Repeat steps (2) to (5) to check another data.

(6) Press the 

TEST

 button for three seconds or press the 

ON/OFF

 button to

deactivate the maintenance mode.

Stable operation
Using the maintenance mode, the operation frequency can be fixed and the op-
eration can be stabilized. If the air conditioner is stopped, use the following pro-
cedure to start this operation.

COOL

STABLE MODE

HEAT

STABLE MODE

STABLE MODE

CANCEL

Stable cooling
operation

Stable heating
operation

Stable operation
cancellation

Display 

Press the 

MODE

 button to select the operation mode.

Press the 

FILTER

 button.

Waiting for
stable operation

Display 

Stable
operation

10-20 min.

* You can check the data using steps (3) to (5) of the maintenance mode opera-

tion procedures while waiting for the stable operation.

Display example (Comp discharge temperature 147    )

Display 

PAR-21MAA

147

.  Installing the grille

Maintenance mode operation procedures

10.   Easy maintenance function (For PUZ-A/PUY-A application only)

 

Only for wired remote cpontroller.

By using the maintenance mode, you can display many types of maintenance data 

on the wired remote controller such as the heat exchanger temperature and com-

pressor current consumption for the indoor and outdoor units.

This function can be used whether the air conditioner is operating or not.

During air conditioner operation, data can be checked during either normal 

operation or maintenance mode stable operation.

*  This function cannot be used during the test run.

*  The availability of this function depends on the connecting outdoor unit. Refer to 

the brochures.

9.7.  Installing the intake grille (Fig. 9-10)

Note:

When reinstalling the corner panels (each with a safety wire attached), con-

nect  the  other  end  of  each  safety  wire  to  the  grille  using  a  screw  (4  pcs,  

 8) as shown in the illustration.

*If the corner panels are not attached, they may fall off while the unit is operating.

• Perform the procedure that is described in “9.2. Preparing to attach the grille” in 

reverse order to install the intake grille and the corner panel.

• Multiple units can be installed with grille so that the position of the logo on each 

corner panel is consistent with the other units regardless of the orientation of the 

intake grille. Align the logo on the panel according to the wishes of the customer 

as shown in the diagram to the left. (The position of the grille can be changed.)

 Refrigerant piping of the main unit
 Drain piping of the main unit
 Position of the corner panel when sent from the factory (logo attached).

* Installation in any position is possible.

 Position of the levers on the intake grille when sent from the factory.

* Although the clips can be installed in any of four positions, the configuration shown here is 

recommended.(It is not necessary to remove the intake grille when maintenance is performed 
on the electric component box of the main unit.)

 Receiver (Only PAR-SA9FA-E)

Screw (4

 

8)

 

Corner panel
Safety wire

Fig. 9-10

(Enlarged)

01_RG79D307K02_EN.indd   15

2010/09/01   11:03:33

Содержание PLA-A-BA4 Series

Страница 1: ...A4 English INSTALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER 01_RG79D307K02_EN indd 1 2010 09 01 11 03 22 ...

Страница 2: ...e gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explosion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wate...

Страница 3: ... The method for using the template and the gauge is shown Before using check the dimensions of template and gauge because they change due to fluctuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance betw...

Страница 4: ...prior to installation of the decorative cover or when applying ceiling materials 3 7 Confirming the position of main unit and tightening the suspension bolts Fig 3 8 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that th...

Страница 5: ...n pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use two wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully B Flare nut tightening tor...

Страница 6: ...ised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 mm 1 1 4 inch PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 mm 1 1 2 inch PVC TUBE for grouped piping 9 mm 23 64 inch or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 850 mm 33 7 16 inch 1 Connect the drain socket supplied with the unit to the drain po...

Страница 7: ...d 6 1 1 Indoor unit power supplied from outdoor unit The following connection patterns are available The outdoor unit power supply patterns vary on models 1 System S1 S2 L N 1 2 S1 S2 S3 S3 A B C D E F G I H CN105 RED S1 S2 L N 1 2 S1 S2 S3 1 2 S1 S2 S3 S3 A B C D E F G G E Affix label A that is included with the manuals near each wiring diagram for the indoor and outdoor units A Outdoor unit powe...

Страница 8: ...ir of an indoor unit PC board and a IR wireless remote controller is assigned to the same pair No 4 IR wireless remote controller pair number setting operation Fig 6 5 Press the SET button with something sharp at the end Start this operation from the status of IR wireless remote controller display turned off MODELSELECT blinks and Model No is lighted Press the min button twice continuously Pair No...

Страница 9: ...n from the status of IR wireless remote controller display turned off CHECK is lighted and 00 blinks Press the temp button once to set 50 Direct the IR wireless remote control ler toward the receiver of the indoor unit and press the h button Setting the unit number Press the temp buttons and to set the unit number 00 Direct the IR wireless remote controller toward the receiver of the indoor unit a...

Страница 10: ...t equipped with outdoor air intake 2 Supported indoor unit is equipped with outdoor air intake 3 Power voltage 230 V 04 104 1 208 V 2 Select unit numbers 01 to 03 or all units AL wired remote controller 07 wireless remote controller Mode Settings Mode No Setting no Initial setting setting Wired remote controller RF thermostat Filter sign 100Hr 07 107 1 2500Hr 2 No filter sign indicator 3 Fan speed...

Страница 11: ...ontrol system error memory error etc No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc IR wireless remote controller Wired remote controller RF thermostat Symptom Remark Beeper sounds OPERATION INDICATOR lamp blinks Number of times Check ...

Страница 12: ...er power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 GR Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and out...

Страница 13: ...er panel Slide the corner panel as indicated by the arrow to remove the corner panel Fig 9 3 Fig 9 4 Intake grille Grille Intake grille levers Grille hook Hole for the grille s hook Corner panel Screw Detail 9 3 Selection of the air outlets For this grille the discharge direction is available in 11 patterns Also by setting the wired remote controller to the appropriate settings you can adjust the ...

Страница 14: ...PLP 42BALM the connector of wireless sensor cable is also connected to connecor CN90 on indoor controller board The lead wire of grille is passed through the catch of bell mouth of the unit perfectly The remaining lead wire is tied with clamp of the unit and put the cover of the unit again with 2 screws Note Do not put the remaining lead wire in electrical branch box of the unit 9 5 Locking the up...

Страница 15: ...on procedures 10 Easy maintenance function For PUZ A PUY A application only Only for wired remote cpontroller By using the maintenance mode you can display many types of maintenance data on the wired remote controller such as the heat exchanger temperature and com pressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not ...

Страница 16: ...handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan RG79D307K02 01_RG79D307K02_EN indd 16 2010 09 01 11 03 34 ...

Отзывы: