11
5. Specifications
Cooling
*1 BTU/h
Capacity
Heating
*1,*3 BTU/h
Heating
*2,*3 BTU/h
Cooling
*1 kW
Heating
*1,*3 kW
Heating
*2,*3 kW
SEER
HSPF
INDOOR UNIT MODELS
External finish
Power supply
V, Phase, Hz
Max. fuse size (time delay)
A
Min. ampacity
A
Fan motor
F. L. A.
Auxiliary heater
A (kW)
Airflow
Dry
CFM
Lo-Hi
Wet
CFM
W
in
Dimensions D
in
H
in
Weight
lbs
OUTDOOR UNIT MODELS
External finish
Power supply
V, Phase, Hz
Max. fuse size (time delay)
A
Min. ampacity
A
Fan motor
F. L. A.
Models
Compressor
R. L. A.
L. R. A.
Crankcase heater
A (W)
Refrigerant control
Defrost method
W
in
Dimensions D
in
H
in
Weight
lbs
REMOTE CONTROLLER
Control voltage
(by built-in transformer)
Item
Models
Power
consumption
NOTES:
*1 Rating conditions (cooling) – indoor: 80°F DB. 67°F WB
outdoor: 95°F DB. 75°F WB
(heating) – indoor: 70°F DB. 60°F WB
outdoor: 47°F DB. 43°F WB
*2 Rating conditions (heating) – indoor: 70°F DB. 60°F WB
outdoor: 17°F DB. 15°F WB
*3 Heating capacity and power consumption in [ ] include auxiliary electric heater operation at 208/230V.
Units should be installed by licensed electric contractor accordingly to local code requirement.
* Specifications subject to change without notice.
PKH18FK3/PKH18FL
PKH24FK3/PKH24FL
PKH30FK3/PKH30FL
PKH36FK3/PKH36FL
18,000
24,000
30,000
34,200
18,600 [24,100/25,100]
25,000 [30,500/31,500]
33,000 [39,100/40,500]
38,000 [44,100/45,500]
10,700 [16,200/17,200]
14,700 [20,200/21,200]
19,000 [25,100/26,500]
19,600 [25,700/27,100]
1.79
2.36
3.12
3.44
1.56 [3.16/3.46]
2.37 [3.97/4.27]
3.02 [4.82/5.22]
3.54 [5.34/5.74]
1.34 [2.94/3.24]
1.92 [3.52/3.82]
2.48 [4.28/4.68]
2.65 [4.45/4.85]
11.1
10.2
10.6
10.5
7.2
6.8
7.1
6.9
PKH18FK3/PKH18FL
PKH24FK3/PKH24FL
PKH30FK3/PKH30FL
PKH36FK3/PKH36FL
Munsell 3.4Y 7.7/0.8
208/230, 1, 60
15
12
13
0.5
0.6
7.6/8.4 [1.6/1.9]
8.7/9.6 [1.8/2.2]
710-530
990-780
640-480
890-700
55-1/8
66-5/32
9-1/4
13-3/8
57
66
PKH18FK3 / PLH18FL
PKH24FK3 / PKH24FL
PKH30FK3 / PKH30FL
PKH36FK3 / PKH36FL
Munsell 5Y 7/1
208/230, 1, 60
20
30
16
20
22
0.75
0.65+0.65
0.75+0.75
RH247NAB
NH33NBD
NH41NAD
NH47NAD
12.0
11.5
14.0
17.5
37
54
73
87
0.11/0.12 (23/28)
0.16/0.17 (33/39)
Capillary tube
Reverse cycle
34-1/4
38-3/16
11-5/8
13-9/16
33-1/2
49-9/16
131
202
245
246
With indoor unit
Indoor unit-remote controller DC12V, Indoor unit- outdoor unit DC12V
All manuals and user guides at all-guides.com