18
Model
Power source
Capacity
Cooling <BTU/h>
Heating <BTU/h>
Dimension (Grille)
H
<inch>
W
<inch>
D
<inch>
Net weight (Grille)
<Ibs>
Fan Airflow range
DRY
<CFM>
(Low-Middle2-Middle1-High)
WET
<CFM>
Noise level
<dB(A)>
(Low-Middle2-Middle1-High)
PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-E
Single 208/230 V 60 Hz
6,000
8,000
12,000
15,000
6,700
9,000
13,500
17,000
9-1/16(1-3/16)
33-5/8(39-3/8)
1/-9/16(18-1/2)
31(7)
230-250-280-300
250-280-300-320
270-300-340-370
200-220-250-270
220-250-270-290
240-270-310-340
27-30-33-35
32-34-36-37
33-35-37-39
■
PMFY Series
Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Note: As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant
leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and comes
into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
Outdoor unit
PUHY
23 °F - 110 °FDB
5 °F - 60 °FWB
Mode
Cooling
Heating
Indoor unit
59 °F - 75 °FWB
59 °F - 81 °FDB
11. Specifications
Model
Power source
Capacity
Cooling <BTU/h>
Heating <BTU/h>
Dimension
H
<inch>
W
<inch>
D
<inch>
Net weight
<Ibs>
Fan Airflow range
DRY
<CFM>
(Low-Middle2-Middle1-High)
WET
<CFM>
Noise level
<dB(A)>
(Low-Middle2-Middle1-High)
PKFY-P06NAMU-E PKFY-P08NAMU-E PKFY-P12NGMU-E PKFY-P15NGMU-E
Single 208/230 V 60 Hz
6,000
8,000
12,000
15,000
6,700
9,000
13,500
17,000
11-5/8
13-3/8
32-1/8
39
6-1/4
9-1/4
19
35
170-180-200-210
280-340-370-410
160-170-180-190
250-300-330-370
32-33-35-36
32-36-40-42
■
PKFY Series
Model
Power source
Capacity
Cooling <BTU/h>
Heating <BTU/h>
Dimension
H
<inch>
W
<inch>
D
<inch>
Net weight
<Ibs>
Fan Airflow range
DRY
<CFM>
(Low-High)
WET
<CFM>
Noise level
<dB(A)>
(Low-High)
PKFY-P18NFMU-E PKFY-P24NFMU-E PKFY-P30NFMU-E
Single 208/230 V 60 Hz
18,000
24,000
30,000
20,000
27,000
34,000
13-3/8
55-1/8
66-1/8
9-1/4
53
62
490-640
780-990
440-570
700-890
39-45
46-49