6. Electrical work
2) For wireless remote controller (Fig. 6-10)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1
Go to the function select mode
Press the
CHECK
button
F
twice continuously.
(Start this operation from the status of remote controller display turned off.)
CHECK
is lighted and “00” blinks.
Press the temp
button
C
once to set “50”. Direct the wireless remote controller
toward the receiver of the indoor unit and press the
h
button
A
.
2
Setting the unit number
Press the temp
button
C
and
D
to set the unit number “00”. Direct the
wireless remote controller toward the receiver of the indoor unit and press the
min
button
B
.
3
Selecting a mode
Enter 04 to change the power voltage setting using the
C
and
D
buttons.
Direct the wireless remote controller toward the receiver of the indoor unit and
press the
h
button
A
.
Current setting number:
1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)
4
Selecting the setting number
Use the
C
and
D
buttons to change the power voltage setting to 01 (240 V).
Direct the wireless remote controller toward the sensor of the indoor unit and press
the
h
button
A
.
5
To select multiple functions continuously
Repeat steps
3
and
4
to change multiple function settings continuously.
6
Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and press
the
button
E
.
Note:
Whenever changes are made to the function settings after installation or
maintenance, be sure to record the changes with a mark in the “Setting”
column of the Function table.
3
CHECK
4
CHECK
ON/OFF
TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESET
SET
CLOCK
CHECK
E
C
,
D
F
A
B
Fig. 6-10
2
CHECK
CHECK
1
6.3.2 Function setting on the remote controller
Refer to the indoor unit operation manual.
Function table
Select unit number 00
Mode
Settings
Mode no.
Setting no.
Initial setting
setting
Power failure automatic recovery
Not available
01
1
*2
Available *1
2
*2
Indoor temperature detecting
Indoor unit operating average
02
1
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
Supported (indoor unit is not equipped with outdoor-air inlet)
2
Supported (indoor unit is equipped with outdoor-air inlet)
3
Power voltage
240 V
04
1
220 V, 230 V
2
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Settings
Mode no.
Setting no.
Initial setting
setting
Filter sign
100Hr
07
1
2500Hr
2
No filter sign indicator
3
Fan speed
Silent
08
1
–
Standard
2
High ceiling
3
–
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
Содержание PKA-RP HAL