24
2. Removing the indoor controller board and
address board
(1) Remove the panel. (Refer to 1.)
(2) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 3.)
(3) Remove the screw of the ground wires connected to the
indoor fan motor (lower), and then the ground wires. (See
Photo 4.)
(4) Remove the screw of the ground wires connected to the
indoor heat exchanger, and then the ground wires. (See
Photo 4.)
(5) Disconnect all the connectors on the address board and
remove the screw of the address board case.
(6) Remove the screw of the ground wire connected to the
indoor controller board, and then the ground wire.
(See Photo 4.)
(7) Pull the indoor controller board case slightly toward you
from the electrical box, and disconnect all the connectors
on the indoor controller board.
(8) Pull out the indoor controller board case from the electrical
box.
OPERATING PROCEDURE
PHOTOS
Terminal block
(TB2)
Screw of the
ground wire (I.B)
Photo 4
3. Removing the electrical box
(1) Remove the panel. (Refer to 1.)
(2) Remove the electrical cover. (Refer to 2.)
(3) Remove the ground wires from the electrical box.
(Refer to 2.)
(4) Remove the ground wires connected to the indoor fan
motor and ones connected to the indoor heat exchanger.
(See Photo 4.)
(5) Remove the screw of the electrical box. (See Photo 4.)
(6) Disconnect the following connectors on the indoor
controller
board.
• Fan motor connectors <CNMF1, 2>
• Vane motor connector <CN6V1>
• Damper motor connector <CN6V2>
• Pipe temperature thermistor connector <CN44>
• Damper limit switch connector <CN36>
(7) Unhook the electrical box from the upper catch and pull out
the electrical box from the box.
Photo 3
Hair pin cover
Water cover Screw of the
electrical cover
Address
board (A.B)
Terminal block(TB5)
Screw of the
ground wire
(Heat exchanger)
Screw of the
ground wire
(Fan motor)
Indoor
controller
board (I.B)
Содержание PFFY Series