background image

4

GB

2.2 Procedures for refrigerant oil recovery

1

Evacuating the existing pipes, and ensuring air tightness

 Charge airtight gas through the service port on both the high-pressure and low-pressure valves. The air tightness should be 

4.15 MPa. After checking the air tightness, evacuate the air through the service port on both the high-pressure and low-pressure valves.

2

Refrigerant charging

 

•If the length or diameter of the refrigerant pipe is unknown
Charge the required amount of refrigerant (indoor units + BC controllers) through both high-pressure and low-pressure service port valves. 
•When refrigerant pipe diameter and length are already known
Charge the required amount of refrigerant (indoor units + BC contr pipes) through both the high-pressure and low-pressure service port
valves. See the table below for the required amount of refrigerant for the indoor units and BC controllers. To calculate the required amount of
refrigerant charged for the pipes, refer to 10.1. “Calculation of additional refrigerant charge” in the installation manual on the CD-ROM. 
If there is excess refrigerant that cannot be charged, use it during oil recovery operation at step 4 (cooling operation).

* After charging the required amount of refrigerant to the existing pipes, open the valve so that the pressure in the existing pipes and outdoor unit

are equal. (Refer to Procedure 3.) Do not open the valve on the outdoor unit when the existing pipes are under vacuum. Doing so may cause
the refrigerant that is dissolved in the refrigerant oil in the compressor to form and cause some oil to migrate to the existing pipes, resulting in
insufficient lubrication.

Procedure 1

High-pressure valve

Low-pressure valve

Procedure 2

High-pressure valve

Low-pressure valve

Total capacity of 

connected indoor units

Charged amount (kg)

- 80

2.0

81 - 160

2.5

161 - 330

3.0

331 - 390

3.5

391 - 480

4.5

Total outdoor unit Model

Charged amount per

BC controller

(Standard / Main) (kg)

P200

2.0

P250

3.0

P300

WT06218X01_en.fm  Page 4  Tuesday, December 14, 2010  4:19 PM

Содержание PERLACE MULTI PURY-RP200YJM-B

Страница 1: ...LLECTE D HUILE MINÉRALE RÉCUPÉRATION DE L HUILE FRIGORIFIQUE MANUAL DE INSTRUCCIONES PARA LA RECOGIDA DE ACEITE MINERAL RECUPERACIÓN DE ACEITE REFRIGERANTE RACCOLTA DELL OLIO MINERALE RECUPERO DELL OLIO REFRIGERANTE MANUALE DI ISTRUZIONI MANUAL DE INSTRUÇÕES DE RECOLHA DE ÓLEO MINERAL RECUPERAÇÃO DO ÓLEO REFRIGERANTE Air Conditioners For Building Application Outdoor Unit PURY RP200 250 300YJM B BS...

Страница 2: ...ort to the refrigerant circuit Evacuation port high pressure side A port through which refrigerant for the indoor units is charged D Service port on the low pressure valve Connecting port to the refrigerant circuit Evacuation port low pressure side A port through which refrigerant for the indoor units is charged E A valve to be closed after the completion of refrigerant oil recovery operation BV3 ...

Страница 3: ...hen the pressure sensor reads 18 8 kg cm2 G Item No 58 The unit of pressure is in kg cm2G Use the following conversion formula to convert the displayed value into a value in SI unit MPa SI unit MPa Displayed value kg cm2 G 0 098 Flag display Each set of two lines in vertical alignment indicates a flag Example Outdoor unit in the 3 minute restart delay mode Item No 14 2 Table of items that can be m...

Страница 4: ... BC controllers To calculate the required amount of refrigerant charged for the pipes refer to 10 1 Calculation of additional refrigerant charge in the installation manual on the CD ROM If there is excess refrigerant that cannot be charged use it during oil recovery operation at step 4 cooling operation After charging the required amount of refrigerant to the existing pipes open the valve so that ...

Страница 5: ...is insufficient the units may stop during refrigerant oil recovery or it may take longer than usual to complete a test run 5Setting the unit address and checking for proper system operation Set the unit address turn on the power and check for proper operation of the system If an attempt is made to operate the outdoor unit before the refrigerant oil recovery operation is complete an error code 7116...

Страница 6: ...igerant charge Do not exceed the maximum amount If the refrigerant oil recovery operation does not finish after the maximum amount of refrigerant is charged close the valve on refrigerant cylinder and wait for the operation to be completed automatically If the cylinder runs out of refrigerant during the refrigerant oil recovery operation continue the operation and replace the cylinder I If more th...

Страница 7: ...pswitches 3 1 and 4 8 to ON in that order S 0 r 0 The refrigerant oil recovery operation is not completed To restart the refrigerant oil recovery operation set the dipswitches 3 1 and 4 8 to ON in that order 8Disconnecting the cylinder After completing the oil recovery operation close the valve on the cylinder and disconnect the cylinder within five minutes 9Recording the amount of refrigerant tha...

Страница 8: ...Electromagnetic Compatibility Directive 2004 108 EC Pressure Equipment Directive 97 23 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STAREET UXBRIDGE MIDDLESEX UB8 1QQ U K WT0621...

Отзывы: