–16–
[2] Bypass Factor Curves
Bypass f
actor
Airflow rate (m
3
/min)
50
55
60
65
70
0.30
0.25
0.20
0.15
0.10
PEH-P8YE
PEH-P10YE
Bypass f
actor
Airflow rate (m
3
/min)
70
75
80
85
90
0.20
0.15
0.10
0.05
0.00
[3] Cooling Sensible Heating Capacity Table
(1) PEH-P8YE (Airflow rate 60m
3
/min)
Outdoor
temp.
(
°
C)
20
25
30
35
40
43
Indoor inlet air temperature (DB/WB
°
C)
CA
18100
17500
16900
16200
15300
14800
SHC
13700
13400
13100
12800
12500
12400
CA
19300
18700
18100
17400
16600
16000
SHC
13500
13300
13000
12700
12400
12300
CA
20000
19500
18900
18000
17400
16900
SHC
14400
13700
13500
13100
13000
12900
CA
20800
20300
19700
19000
18200
17700
SHC
14400
14200
14000
13700
13500
13400
CA
21900
21500
20900
20200
19500
19000
SHC
14200
13900
13700
13500
13300
13200
23/16
25/18
27/19
28/20
30/22
(2) PEH-P10YE (Airflow rate 80m
3
/min)
Outdoor
temp.
(
°
C)
20
25
30
35
40
43
Indoor inlet air temperature (DB/WB
°
C)
CA
22500
21800
21000
20100
19100
18400
SHC
18100
17800
17500
17100
16800
16600
CA
24000
23300
22500
21600
20600
20000
SHC
17900
17600
17300
16800
16600
16500
CA
24900
24300
23500
22400
21600
21000
SHC
18500
18300
17900
17400
17400
17300
CA
25800
25200
24500
23600
22700
22000
SHC
19200
18900
18600
18300
18100
18000
CA
27300
26700
26000
25200
24200
23600
SHC
18800
18600
18300
18100
17900
17800
23/16
25/18
27/19
28/20
30/22