8. Electrical work
Function table 1
Select unit number 00
Function table 2
Select unit numbers 01 to 04 or all units (AL [wired remote controller]/07 [wireless remote controller])
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
Mode
Settings
Mode no.
Setting no.
Initial setting
Check
Power failure automatic recovery
(AUTO RESTART FUNCTION)
Not available
01
1
*2
Available
*1
2
*2
Indoor temperature detecting
Indoor unit operating average
02
1
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
Supported (indoor unit is not equipped with outdoor-air intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
240V
04
1
220V, 230V
2
Auto mode
Energy saving cycle automatically enabled
05
1
Energy saving cycle automatically disabled
2
Mode
Settings
Mode no.
Setting no.
Initial setting
Check
Filter sign
100 Hr
07
1
2500 Hr
2
No filter sign indicator
3
External static pressure
08
1
2
3
10
1
2
3
Note:
When the function of an indoor unit were changed by function selection after the end of installation, always indicate the contents by entering a
or other mark in the
appropriate check filed of the tables.
External static pressure
Setting no. of
mode no. 08
Setting no. of
mode no. 10
35 Pa
2
1
50 Pa (before shipment)
3
1
70 Pa
1
2
100 Pa
2
2
150 Pa
3
2