20
7-2. FUNCTION OF DIP SWITCH
PCFY-P40VGM-E PCFY-P63VGM-E PCFY-P100VGM-E PCFY-P125VGM-E
1
2
3
4
5
6
7
8
9
10
1~6
1
2
3
4
5
6
7
8
9
10
1~4
Room temperature Thermistor
position
ON
OFF
Filter clogging detection
Provided
Not provided
Filter cleaning sign
2500hr
100hr
Air intake
Effective
Not effective
Remote indication switching
Thermostat ON signal indication Fan output indication
Humidifier control
Always operated while the heating mode
w
1
Operated depends on the condition
w
2
Air flow set in case of
Fix to LOW
w
3
Fix to EXTRA lOW
w
3
heat thermostat OFF
Depends on setting remote controller
w
3
Depends on SW1-7
Auto reset function
Effective
Not effective
Power resource ON/OFF
Effective
Not effective
Heat pump/Cool only
Cooling only
Heat pump
Louver
Available
Not available
Vane
Available
Not available
Vane swing function
Available
Not available
Vane horizontal angle
Second setting
First setting
Vane cooling limit angle setting
w
4
Horizontal angle
Down B,C
Effective
Not effective
Heater 4degrees up
Not effective
Effective
Target Superheat setting
w
5
9degrees
6degrees
Target Subcool setting
15degrees
10degrees
ON
OFF
ON
OFF
1 2 3 4 5
1 2 3 4 5
ON
OFF
1 2 3 4 5 6 7 8 9 10
ON
OFF
1 2 3 4 5 6 7 8 9 10
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
Capacity
SW2
Capacity
SW2
Capacity
SW2
PCFY-
P40VGM-E
PCFY-
P63VGM-E
PCFY-
P100VGM-E
PCFY-
P125VGM-E
Address board
<At delivery>
Indoor controller board
Indoor controller board
Indoor controller board
<At delivery>
<At delivery>
SW4
Unit
Selection
SW3
Function
Selection
SW2
Capacity
code
setting
SW1
Mode
Selection
Switch Pole
Function
Remarks
Operation by switch
Built-in remote controller
Indoor unit
Indoor linear expansion
valve opening
NOTE:
w
1 At Heating mode, fan
operating.
w
2 At Heater mode, operating
heat thermostat ON.
w
3 SW1-7=OFF, SW1-8=ON
→
Setting air flow.
SW1-7=ON, SW1-8=ON
→
Indoor fan stop.
Set while the unit is off.
<At delivery>
Set for each capacity.
Set while the unit is off.
NOTE:
w
4 At cooling mode, each
angle can be used only 1
hour.
w
5 SW3-9 setting
P40 = ON
P63,P100,P125 = OFF
Set while the unit is off.
OC308A--1.qxp 06.7.7 3:45 PM Page 20