11
Service Ref.
Item
Btu/h
W
W
kW
kW
A
A
kW
K
/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Fan(drive) x No.
Fan motor output
Airflow(Low-Med2-Med1-High)
External static pressure
Operation control & Thermostat
Noise level(Low-Med2-Med1-High)
Unit drain pipe O.D.
Dimensions
Weight
W
D
H
INDOOR UNIT
PCA-RP6GA
PCA-RP6GA
Cooling
47,800
14,000(6,200~15,300)
14,000(5,500~15,300)
4.96
0.22
1.01
2.20
Heating
54,600
16,000(6,200~18,000)
16,000(5,000~18,000)
4.60
0.22
1.01
2.20
Single phase, 50Hz, 220-230-240V
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 4
0.150
27-30-32-34(955-1,060-1,130-1,200)
0(direct blow)
Remote controller & built-in
42-44-46-48
26(1)
1,620(63-3/4)
680(26-3/4)
270(10-5/8)
45(99)
Service Ref.
OUTDOOR
UNIT
PUHZ-RP6VHA
PUHZ-RP6VHA
1
PUHZ-RP6VHA
PUHZ-RP6VHA
1
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Outdoor
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor
: D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
4. Above data based on indicated voltage
Indoor Unit Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C
Cooling
Heating
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
3. Guaranteed voltage
198~264V, 50Hz
Cooling
42,700
12,500(6,000~14,000)
12,500(5,500~14,000)
3.89
0.22
1.01
2.20
Heating
47,800
14,000(6,000~16,000)
14,000(5,000~16,000)
4.34
0.22
1.01
2.20
Single phase, 50Hz, 220-230-240V
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 4
0.150
27-30-32-34(955-1,060-1,130-1,200)
0(direct blow)
Remote controller & built-in
41-43-45-46
26(1)
1,620(63-3/4)
680(26-3/4)
270(10-5/8)
43(95)
PCA-RP5GA
PCA-RP5GA
Service Ref.
Item
Btu/h
W
W
kW
kW
A
A
kW
K
/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Fan(drive) x No.
Fan motor output
Airflow(Low-Med2-Med1-High)
External static pressure
Operation control & Thermostat
Noise level(Low-Med2-Med1-High)
Unit drain pipe O.D.
Dimensions
Weight
W
D
H
Service Ref.
INDOOR UNIT
OUTDOOR
UNIT
PUHZ-RP5VHA
PUHZ-RP5VHA
1
PUHZ-RP5VHA
PUHZ-RP5VHA
1