![Mitsubishi Electric PCA-P3HA Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/mitsubishi-electric/pca-p3ha/pca-p3ha_technical-and-service-manual_1811396019.webp)
19
Air flow
Air speed
Coverage range
m
3
/min
m/sec
m
19
2.9
7.9
38
4.2
13.2
PCA-P3HA
PCA-P5HA
4. OUTLET AIR SPEED AND COVERAGE RANGE
3.2 Cooling only type
Rating Conditions (ISO T1)
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(
O
O
f/
F
F
)
Electrical circuit
Total
Refrigerant circuit
Indoor side
Outdoor
side
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Mode
Service Ref.
SHF
BF
W
KW
V
A
V
A
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
Cooling
7,500
3.36
PCA-P3HA
1, 50
230
0.43
PU-P3VGAA
1
.UK
/PU-P3YGAA
1
.UK
1, 50/3, 50
230/400
14.63/4.96
84
59
2.9
5
27
19
13
35
24
0.72
0.14
2.31
(23.5)
0.45
(4.6)
MPa
(
O
f/
F
)
MPa
(
O
f/
F
)
D.B.
W.B.
D.B.
D.B.
W.B.
PCA-P3HA
Cooling
13,000
4.90
PCA-P5HA
1, 50
230
1.19
PU-P5YGAA
1
.UK
3, 50
400
6.85
73
54
4.8
5
27
19
15
35
24
0.75
0.19
2.01
(20.5)
0.46
(4.6)
PCA-P5HA
OC289--1.qxp 03.3.19 10:50 AM Page 19