– 15 –
(2) Setup screen
After completing the settings, touch the [Back] button on the [Setup] screen. The message “Collecting
the information from the air conditioner.” will appear, and then the screen will jump to the HOME screen.
This signals the completion of the setup process.
Access the Service Menu from the HOME screen to make the settings for other items as necessary.
(a) Group setting
Use this screen to register the indoor units and the AHC to be controlled from the controller.
1
Select an indoor unit or an AHC address in the
[Address] field.
The number of units that can be registered.
Indoor unit: 16 units maximum
AHC: 1 unit maximum
* AHC cannot be controlled from the controller unless indoor
units are registered with the system.
2
Touch the [Set] button to register the address, and
[Del] to delete the address.
• Successful address registration/deletion:
The registered address(es) will appear on the left
side of the screen.
Deleted address will not appear on the screen.
• Error:
"Request denied." or "Is not to be connected" will
appear.
(b) Interlocked LOSSNAY
Use this function to interlock the operation of indoor units and LOSSNAY units.
1
To register LOSSNAY units
Select the indoor unit address in the Add. 1 section.
Select the interlocked LOSSNAY address in the Add. 2
section. Touch the [Set] button to save the setting.
2
To search for an interlocked setting
Touch the [Conf] button to display in the left column
the addresses of the units that are interlocked with the
unit whose address was set in the Add. 1 section.
3
To delete the interlock settings
After taking Step
2
above, select the address to be
deleted in the Add. 2 section, and then touch the [Del]
button.
(c) Search connection information
Use this screen to specify a unit and search for the controllers that are connected to the unit.
1
Select an address in the [Address] field.
2
Touch the [Conf] button to search for the interlocked
units.
The results will appear in the left column. (When
multiple units are found, the addresses that do not fit
on the first page will appear on the successive pages.)
• Search error:
"Request denied." will appear.
When the setting or deletion is successfully completed, “Completed” will appear below
[Function] field on the screen.
If setting or deletion fails, “Request denied” will appear below [Function] field on the screen.
WT06829X02.book Page 15 Wednesday, June 26, 2013 4:03 PM
Содержание par-u02meda
Страница 21: ... 20 k Reset RC l AHC port name 2 Error Menu a Self check max 20 characters ...
Страница 49: ... 24 2 Menu d erreurs a Auto contrôle ...
Страница 102: ... 23 2 Menu errori a Autodiagnosi ...
Страница 105: ... 26 ...
Страница 129: ... 22 k Restaurar CR l Nome da porta AHC 2 Menu de erro a Self Check máx 20 caracteres ...
Страница 158: ... 25 2 Μενού Error σφαλμάτων a Self check αυτοδιάγνωση ...
Страница 161: ... 28 ...
Страница 185: ... 22 2 Error Hata Menüsü a Self check Kendiliğinden kontrol ...
Страница 212: ... 23 2 Meni Error napaka a Self check samodejni pregled ...
Страница 215: ... 26 ...
Страница 239: ... 22 2 Izbornik Error Pogreška a Self check Samoprovjera ...
Страница 266: ... 23 2 Meniul Error Eroare a Self check Verificare individuală ...
Страница 269: ......
Страница 270: ......
Страница 271: ......