6 Model Select
7 Test Run
8 Pair Number Setting
This remote controller needs model number setting before use.
Set the model number in the following order.
Without setting, the air conditioner will not work properly. (The factory setting of model number is 001 .)
①Press the SET button with the point of a ball-point pen or the like.
MODEL SELECT blinks and model number 001 is lighted.
Start this operation from the status of remote controller display turned off.
② Press the TEMP , buttons and set the model number according to the lndoor unit model.
(See Table 1 )
③Press the SET button with the point of a ball-point pen or the like.
MODEL SELECT and model number are lighted for 3 seconds, then turned off.
①Press the TEST RUN button twice continuously.
TEST RUN and current operation mode are displayed.
Start this operation from the status of remote controller display turned off.
②Press the MODE button.
Operation mode switches between cooling mode and heating mode.
Cooling mode…Check outlet of cool airflow.
Heating mode…Check outlet of warm airflow.(This action takes some time.)
③Press the FAN button.
Check if the fan speed changes.
④Press the VANE button.
Check if the automatic vane is working.
⑤Press the ON/OFF button or press the TEST RUN button twice continuously.
Test run will be canceled.
This is the setting to specify the unit to operate with the wireless
remote controller.
Make setting for J41,J42 (Jumper wire) of indoor controller board and
the pair number of wireless remote controller.
The pair number setting is available with the 4 patterns as shown in
the〈Table 2〉 from A to D. Make setting for the pair number (J41,J42)
of indoor controller board and the pair number of wireless remote
controller which is used as shown in the
〈Table 2〉.
※The factory setting is pattern A.
[Setting procedure for pair number of wireless remote controller]
①Press the SET button with the point of a ball-point pen or the like.
MODEL SELECT blinks and model number is lighted.
Start this operation from the status of remote controller display
turned off.
②Press the min button twice continuously.
Pair number 0 will blink.
③Press the TEMP , buttons and set the pair number according to
the setting pattern.(See Table 2)
④Press the SET button with the point of a ball-point pen or the like.
Pair number is lighted for 3 seconds, then turned off.
〈Table 1 〉
Heat pump
Cooling only
001
033
Model No.
(H/P)/(C/O)
ON/OFF
TEMP
FAN
MODE
LOUVER
VANE
CHECK
TEST RUN
AUTO START
MODEL
SELECT
AUTO STOP
h
SET
RESET CLOCK
min
Model number
②
①③
ON/OFF
TEMP
FAN
MODE
LOUVER
VANE
CHECK
TEST RUN
AUTO START
TEST
RUN
COOL
FAN
AUTO STOP
h
SET
RESET CLOCK
min
②
①⑤
⑤
③
④
ON/OFF
TEMP
FAN
MODE
LOUVER
VANE
CHECK
TEST RUN
AUTO START
MODEL
SELECT
AUTO STOP
h
SET
RESET CLOCK
min
Model number
Pair Number
②
①④
③
A
B
C
D
0
1
2
3〜9
Don't cut the jumper wire.
Cut the jumper wire J41 .
Cut the jumper wire J42 .
Cut the jumper wire both
J41 and J42
Setting
Pattern
Pair number of
Wireless remote
controller
Cut point of Jumper wire
on the indoor controller board
〈Table 2〉
(
1
)
Same setting
●
All units can be operated with the same wireless remote controller.
(
2
)
Individual setting
●
Each unit can be operated with only the wireless remote controller which the same pair number was set.
Pair number 1
Wireless remote controller
Indoor unit
receiver
section
receiver
section
receiver
section
receiver
section
Indoor unit
Pair number 2
Wireless remote controller
Pair number 3
Wireless remote controller
Pair number 0
Wireless remote controller
Indoor unit
Indoor unit
Pair number 0
Pair number 1
Pair number 2
Pair number 3
●
The pair number of indoor controller
board and wireless remote controller
should be set identically.
●
All units should be installed in a
range that the sensor can receive the
signal from wireless remote controller.
Or an operator of wireless remote
controller should move to the proper
position to operate wireless remote
controller.
●
The indoor controller board and the
wireless remote controller should be
set to pair number differently per unit.
Indoor unit
Pair number 0
Pair number 0
Indoor unit
Pair number 0
Wireless remote controller
Indoor unit
Indoor unit
receiver
section
receiver
section
receiver
section
receiver
section
Pair number 0
Pair number 0