![Mitsubishi Electric PAC-WHS01HC-E Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/mitsubishi-electric/pac-whs01hc-e/pac-whs01hc-e_installation-manual_1811821012.webp)
EN-11
English
5. Functions of Switch and LED
5
–
1. Function Setting Switch (SW1)
5
–
2. Emergency Operation Switches (Ch1, 2, 3, 4)
5
–
3. LED Function
SW No
Function
ON
OFF
SW 1–1 Switching initial close/open of Ch1 contact
Ch1: Contact is close
Ch1: Contact is open
SW 1–2 Switching initial close/open of Ch2 contact
Ch2: Contact is close
Ch2: Contact is open
SW 1–3 Switching initial close/open of Ch3 contact
Ch3: Contact is close
Ch3: Contact is open
SW 1–4 Switching initial close/open of Ch4 contact
Ch4: Contact is close
Ch4: Contact is open
SW 1–5 Switching the connection status of indoor units
Without indoor unit connection With indoor unit connection
SW 1–6 Switching wet contact/dry contact of Ch3
Ch3: Wet contact
Ch3: Dry contact
SW 1–7 Switching wet contact/dry contact of Ch4
Ch4: Wet contact
Ch4: Dry contact
SW 1–8
not use
No
Description
LED1
LED2
LED3
LED4
LED5
LED6
LED7
1
Starting up for 3 seconds
(0.5–sec
interval)
(0.5–sec
interval)
(0.5–sec
interval)
(0.5–sec
interval)
(0.5–sec
interval)
(0.5–sec
interval)
(0.5–sec
interval)
2
Equipment connected to Ch1 is
permitted to operate (Contact: Close)
-
-
-
-
-
-
3
Equipment connected to Ch2 is
permitted to operate (Contact: Close)
-
-
-
-
-
-
4
Equipment connected to Ch3 is
permitted to operate (Contact: Close)
-
-
-
-
-
-
5
Equipment connected to Ch4 is
permitted to operate (Contact: Close)
-
-
-
-
-
-
6
Outdoor temperature sensor: Normal
-
-
-
-
-
-
7
Outdoor temperature sensor: Fault
-
(0.5–sec
interval)
-
-
-
-
(0.5–sec
interval)
8
Outdoor temperature sensor: Not
connected
-
-
-
-
-
-
9
Initiating communication with the indoor
unit
-
-
-
-
-
-
10
Communicating with the Wireless
Interface or indoor unit
(0.1–sec
blinking)
-
-
-
-
-
-
Switch state
Function
ON
Closes Ch1, 2, 3, 4 contact and permits equipment operation.
AUTO
Remotely sets an open/close status of Ch1, 2, 3, 4 contact.
OFF
Opens Ch1, 2, 3, 4 contact and prohibits equipment operation.
1) Turn OFF the power supply of the product before switching the Function Setting Switch.
2) Set the Function Setting Switch (SW1) properly according to the Equipment Controller’s usage.
● Set SW1–1 to 1–4 to change the initial state of relay contact for safety.
Equipment Controller will reset if it doesn’t communicate to Wireless Interface for several minutes.
After that, relay contact state will become state indicated by these SW1–1 to 1–4.
Recommended settings vary depending on the equipment connected to each Ch.
Refer to kumocloud.com/resources for details.
● Set SW1–6 and 1–7 to ON or OFF according to the power supply status to the connecting equipment of Ch3 and 4.
● Set SW1–5 to ON when the Equipment Controller is not connected to an indoor unit.
The Emergency Operation Switches provide an ability to override the output status
of the 4 Equipment Controller outputs which control connected equipment.
To operate the equipment from kumo cloud™, set switch state to “Auto”.
: ON
: OFF
: Blinking
- : N/A
Ch1 Ch2 Ch3 Ch4
Emergency
Operation
Switches
LED1 to 6 : Green
LED7 : Orange
Note: If changing the setting of the Emergency Operation Switches of the Equipment Controller
does not change the relay contact output, please contact your contractor for service.