Unit selection
• Registering a unit in a group
1
The address is incremented each time the TEMP.
switch is pressed, and decremented each
time the
switch is pressed. (The skip function operates if the switch is pressed for more than
three seconds.)
NOTE: The setting ranges for addresses for the various types of registered units are as shown below.
Indoor units and ventilation units : 001 - 050
Local remote controllers
: 101 - 200
Slave system controllers
: 000, 201 - 250
* When a unit registered in another group is selected the group select display ( ) for the already
registered group blinks.
2
Press the
switch to register the selected unit in the group.
• The unit type is displayed when registration is completed normally.
Indoor units
: IC
Ventilation unit
: LC
Local remote controller : RC
System controller : SC
• [
] blinks if registration fails.
ON
COLLECTIVE
GROUP
OFF
CENTRALIZED
AUTO
BY-PASS
HEAT EX.
CHECK
FILTER
PROHIBIT
MODE LOCK
FILTER
SKIP
TEMP.
MODE
ON/OFF
˚C
ON/OFF
Registration complete screen
The indoor unit with address 006 is registered in group 3.
3
Repeat (2) above to register a different unit in the same group. To register in a different group,
select the group and then repeat (1) and (2) above.
NOTE: • Indoor units and ventilation units cannot be registered in the same group. If registration is at-
tempted, [
] is displayed and registration does not proceed.
• When indoor units, ventilation units, and local remote controllers have already been registered in
a different group, they cannot be registered in another group. (Slave system controllers may be
registered in multiple groups.)
Type (eg [
]) displayed if registration is completed normally.
Address to be registered displayed here.