background image

7

CENTRALIZED CONTROL

M1 M2 S

M1

M2

S

3

4.Installation procedure 

【 

Applicable model:Group B 

8

Lead wire-B

8

Lead wire-B

1

M-NET board

1

M-NET board

5

Terminal Screw

              (M4

o

25)

4

Terminal block

4

Terminal block

6

Label

9

Ground wire and screw

(Note 1) See the Caution on page 2

7

Lead wire-A

7

Lead wire-A

0

Fastener

CN2M

Control P.C. board holder (Back)

Control P.C. board

Control P.C. board holder

Screw

CN5

CN741

【 

w

【 

w

【 

w

  Pass 

Lead wire-A and 

Lead wire-B through the upper clips (right side) on the 

            control P.C. board holder.

【 

w

  Pass 

Lead wire-B through the right clips (upper side) on the control P.C. board holder.

1

 

Remove the two screws and remove the 

    control P.C. board holder.

4

 

Use the two screws removed previously 

    to install the control P.C. board holder in

    the previous position.

6

 

Attach 

Label to the position shown in 

    the figure.

8

 

Refer to the wiring diagram, and connect 

    the 

Lead wire-B that you previously 

    connected to CN2M on the 

M-NET board 

    to the M1 and M2 terminals on the 

     ④

Terminal block.

    There is no polarity difference.

9

 

Bundle the front and back of the coil 

    sections of 

Lead wire-B using the 

    ⑩

Fasteners as shown in the figure.

(Note 1)

If required, connect the shield of the M-NET 

transmission wire to the main unit using the 

Ground wire and screw (M4 x8). 

(See the Caution on page 2)

(Note 2)

Take great care that no lead wire is caught

on anything when installing panels.

7

 

Refer to the wiring diagram, and connect 

    the 

Lead wire-A that you previously 

    connected to CN5 on the 

M-NET board 

    to CN741 (Color: Red) on the control 

    P.C. board.

5

 

Use the 

Terminal screw (M4 x 25) to fix 

    the 

Terminal block in the position shown

    in the figure. 

    

w

The 

Terminal block has a boss for

      positioning. Align the boss with the positioning 

      hole on the metal plate.

3

 

Install the 

M-NET Board to which the 

    wires were attached in the previous step 

    to the back of the control P.C. board holder.

    

w

Set the addresses on the 

M-NET Board 

      before installing into the electrical parts box. 

    

w

Be sure that the M-NET board is installed 

      in the correct orientation (so that the CN2M 

      is upwards and CN5 is downwards).

2

 

Attach 

Lead wire-A to CN5 (Color: White) 

    on the 

M-NET Board and 

Lead wire-B to

    CN2M (Color: White) on the 

M-NET Board.

1

2

2

3

4

5

6

7

8

9

Control P.C. board

Содержание PAC-IF01MNT-E

Страница 1: ...rce of the cable Faulty connections can cause heat or fire The terminal cover panel of the unit must be installed securely Faulty installation can cause fire or electric shock by dust or water The electric installation must be done by qualified person in accordance with this installation manual Use the separate circuit only for this machine and use rated voltage and circuit breaker If the electric...

Страница 2: ... two or more locations electrical circuit is generated through them and a potential difference is created because of the impedance difference between or among the ground locations This may cause noise in the shield Ground at only one point then no circuit is created and no noise gets in w2 In case that the outdoor unit is grounded connect the ground wire supplied as accessory to the S terminal sec...

Страница 3: ...1 Never supply voltage 208V 230VAC to the terminals for M NET transmission If the voltage is supplied it can break the electronic parts on the M NET board 2 Use the shielded cable CVVS CPEVS MVVS of 1 25mm AWG 16 with 2 wires polarity is not a concern for the transmission cable Never use transmit wires of different system with a cable which contains multi wires The communication of transmit signal...

Страница 4: ... be set within the range of 01 to 50 For instance when the head address set with SW11 and SW12 is 47 and you are to connect 5 indoor units A B C D E the addresses for each indoor unit are A 47 B 48 C 49 D 50 and E 51 Since the number for E exceeds 50 this setting is not available w Ex MXZ 5C42NA Outdoor unit M1 S M2 M NET board A unit B unit C unit D unit E unit Indoor unit Indoor unit Indoor unit...

Страница 5: ...em controller system controller A B Power supply unit for transmit cable A B S Outdoor unit M1 S M2 M NET board A unit B unit C unit D unit E unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Group B Group C Group D Group E Group A system controller A B Power supply unit for transmit cable A B S Outdoor unit M1 S M2 M NET board A unit B unit C unit D unit E unit Indoor unit Indoor u...

Страница 6: ... the M1 and M2 terminals on the Terminal block There is no polarity difference Note 1 If required connect the shield of the M NET transmission wire to the main unit using the Ground wire and screw M4 x8 See the Caution on page 2 Note 2 Take great care that no lead wire is caught on anything when installing panels 7 Refer to the wiring diagram and connect the Lead wire A that you previously connect...

Страница 7: ...ifference 9 Bundle the front and back of the coil sections of Lead wire B using the Fasteners as shown in the figure Note 1 If required connect the shield of the M NET transmission wire to the main unit using the Ground wire and screw M4 x8 See the Caution on page 2 Note 2 Take great care that no lead wire is caught on anything when installing panels 7 Refer to the wiring diagram and connect the L...

Страница 8: ...PAC IF01MNT E List of Models on separate sheet BT79C388H01 Group Applicable model Page A MXZ 3C24NA MXZ 3C30NA MXZ 4C36NA B MXZ 2C20NAHZ MXZ 3C24NAHZ MXZ 3C30NAHZ MXZ 5C42NA ...

Страница 9: ......

Отзывы: