System
controller
A
B
Power supply
unit
for transmit
Outdoor unit
M1
S
M2
M-NET board
A unit
B unit
C unit
D unit
Indoor unit
MA
Indoor unit
MA
Indoor unit
MA
Indoor unit
RC
w
Ex)MXZ-4C36NA indoor units maximum connection.
A B S
Outdoor unit
M1
S
M2
M-NET board
A unit
B unit
C unit
D unit
E unit
Indoor unit
MA
Indoor unit
MA
Indoor unit
MA
Indoor unit
MA
Indoor unit
RC
w
Ex)MXZ-5C42NA indoor units maximum connection.
200m (656 ft) or less
MA : MA remote controller
RC :Wireless remote controller
Caution for wiring
1
Never supply voltage 208V-230VAC to the terminals for M-NET transmission. If the voltage is supplied,
it can break the electronic parts on the M-NET board.
2
Use the shielded cable (CVVS, CPEVS, MVVS) of 1.25mm² (AWG 16) with 2 wires (polarity is
not a concern) for the transmission cable.
Never use transmit wires of different system with a cable which contains multi wires.
The communication of transmit signals will not work properly and it can cause wrong operation.
2. Wiring method for M-NET
3
3
The power consumption coefficient of the M-NET board is “1”.
w
1 “Power consumption coefficient” is a coefficient to calculate the relative power
consumption of the devices that receive power through the M-NET transmission cable.
w
1
Содержание PAC-IF01MNT-E