This chapter describes the specifications of the D/A converter module.
3.1
General Specifications
*1
Do not use or store the D/A converter module under pressure higher than the atmospheric pressure at an elevation of 0
meters. Doing so may cause malfunction. When using the D/A converter module under pressure, please consult your
local Mitsubishi representative.
*2
If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the
module can be used even outside the control panel.
*3
This indicates the assumption that the equipment is connected to which type of power distribution system, from the
public electrical power distribution network down to machinery within premises.
Category
applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand
level for the equipment with up to the rated voltage of 300V is 2500V.
*4
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
In pollution degree 2, only non-conductive pollution occurs. A temporary conductivity caused by condensation must be
expected occasionally.
For compliance with the EMC Directive, refer to "EMC and Low Voltage Directives" in this manual. (
Item
Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
Operating ambient
humidity
5 to 95%RH, non-condensing
Storage ambient
humidity
Vibration resistance
Compliant with JIS
B 3502 and IEC
61131-2
Frequency
Constant
acceleration
Half amplitude
Number of sweeps
Under intermittent
vibration
5 to 8.4Hz
3.5mm
10 times each in X,
Y, and Z directions
8.4 to 150Hz
9.8m/s
2
Under continuous
vibration
5 to 8.4Hz
1.75mm
8.4 to 150Hz
4.9m/s
2
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
2
, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gases
Operating altitude
0 to 2000m
Installation location
Inside a control panel
Overvoltage
category
or less
Pollution degree
2 or less
Equipment class
Class