background image

7

A

Die

Copper pipe

Flare nut

Die

Copper pipe

Smooth all around

Even length
all around

Inside is shining without any scratches

York

4. Flaring work

• Perform flaring work using flaring tool as shown in the right.

A (mm)

Outside diameter Flare tool for R410A

Conventional flare tool

clutch type

Clutch type

Wing nut type

ø6.35 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø9.52 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø12.7 mm

0 to 0.5

1.0 to 1.5

2.0 to 2.5

ø15.88 mm

0 to 0.5

1.0 to 1.5

Firmly hold copper pipe in a die in the dimension shown in the
table above.

5. Check

• Compare the flared work with the figure below.
• If flare is noted to be defective, cut off the flared section

and perform flaring work again.

5-3

PIPE CONNECTION

Note:
Fasten a flare nut with a torque wrench as specified in the table below.
When fastened too tight, a flare nut may broken after a long period and cause a leakage of refrigerant.

1. Indoor unit connection

• Connect both liquid pipe and gas pipe to indoor unit.

- Apply a thin coat of refrigeration oil to the seat surface of pipe.
- For connection, align the center of both pipe and union, then tighten the first 3 to 4 turns in flare nut by

hand.

- For tightening the union part of the indoor unit side, use the table below as a standard and tighten

the flare nut with two wrenches. Excessive tightening damages the flared section.

Pipe diamete

Tightening torque

N·m

kgf·cm

ø6.35 mm

13.7 to 17.7

140 to 180

ø9.52 mm

34.3 to 41.2

350 to 420

ø12.7 mm

49.0 to 56.4

500 to 575

ø15.88 mm

73.5 to 78.4

750 to 800

2. Outdoor unit connection

• Connect pipes to the pipe joint part of the stop valve in the same method as the indoor unit.

- For tightening, use the same tightening torque applied for indoor unit and tighten the flare nut with

torque wrench or spanner.

INSULATION AND TAPING

1

Cover piping joints with pipe cover.

2

For outdoor unit side, surely insulate every piping including valves.

3

Using piping tape 

E

, apply taping starting from the entry of outdoor unit.

• Fix the end of piping tape 

E

 with adhesive tape.

• When piping has to be arranged through above ceiling, closet or area where the temperature and humidity

are high, wind additional commercially sold insulation for prevention of condensation.

5-4

PURGING PROCEDURES • LEAK TEST

• Perform the manifold valve work securely according to the installation manual of the manifold valve.

Flaring tool

Wing nut type

Clutch type

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and gas pipe) between the indoor and
the outdoor unit.

Remove the service port cap of the stop valve on the gas pipe side of the outdoor unit.
(The stop valve will not work in it initial state fresh out of the factory [totally closed with
cap on].)

Connect the gauge manifold valve and the vacuum pump to the service port of the stop
valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold valve
and stop the vacuum pump.

Leave it as is for one or two minutes. Make sure the pointer of the gauge manifold
valve remains in the same position. Confirm that the pressure gauge shows –0.101
MPa [Gauge] (–760 mmHg).

Pipe length up to 40 m
No gas charge is needed.

Pipe length exceeding 40 m
Charge the prescribed
amount of gas. (refer to 5-1)

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on both
sides of gas pipe and liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

(or the vacuum
pump with the
function to prevent
the back flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose (for R410A)

Vacuum
pump

Adapter for
preventing
the back flow

Charge hose
(for R410A)

Stop valve
(gas side)

Service port

Содержание MXZ-A26

Страница 1: ...LATION DIAGRAM ACCESSORIES 2 3 SELECTING THE INSTALLATION LOCATION 3 4 OUTDOOR UNIT INSTALLATION 4 5 INDOOR OUTDOOR UNITS CONNECTION FINISHING AND TEST RUN 6 HFC utilized R410A IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS 3000 S A A WIRING RULES THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR ...

Страница 2: ...ing works It could cause an electric shock The appliance shall be installed in accordance with national wiring regulations When installing or relocating the unit make sure that no substance other than the speci fied refrigerant R410A enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise or an explo sion More than 100 mm Open as a rule More th...

Страница 3: ...alling in a place with less strength may result in a unit falling causing a risk of injury CAUTION Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wire less equipment on onne...

Страница 4: ...ocket to the hole 2Please close the rest of the holes with the drain caps 3Please connect a vinyl hose of 25 mm in the inside diameter on the market with the drain socket and lead drain 4 3 HOW TO REMOVE THE SERVICE PANEL AND THE CONNECT COVER Remove the four service panel securing screws and pull the panel down in an arrow direction to remove the service panel Remove the four connect cover securi...

Страница 5: ... and Outdoor connecting wire Specification Cable 2 core 1 0 1 5 mm2 in conformity with Design 245 IEC 57 This installation manual is only for the outdoor unit installation In installing the indoor units refer to the installation manual attached to each indoor unit WARNING Use the indoor outdoor unit connecting wire that meets the Standards to connect the indoor and out door units and fix the wire ...

Страница 6: ... connecting the model 12 13 or 18 to either unit A or B for MXZ A32WV and B or C for MXZ A26WV use optional different diameter joints MAC A454JP because the valve size of gas pipes for the outdoor unit is ø9 52 mm No need to use different diameter joints if the diameter of the pipe is ø9 52 mm When connecting the model 07 or 09 to either unit A or B for MXZ A32WV and A for MXZ A26WV use optional d...

Страница 7: ...top valve on the gas pipe side of the outdoor unit The stop valve will not work in it initial state fresh out of the factory totally closed with cap on Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit Run the vacuum pump Vacuumize for more than 15 minutes Check the vacuum with the gauge manifold valve then close the...

Страница 8: ... of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam Indoor unit Union Stop valve Outdoor unit Union Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder operating valve for R410A Refrigerant gas cylinder for R410A with siphon Refrigerant liquid Electronic scale for refrigerant charging Liquid pipe Gas p...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SG79Y347H01 ...

Отзывы: