background image

En-5

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3-1. FLARING WORK

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool  

for R410A

Clutch 

type tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35 (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø9.52 (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7 (1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88 (5/8”)

29

73.5 to 78.4 750 to 800

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes 

and the pipe connections of the outdoor unit. Do not apply refrigeration 
oil on screw threads. Excessive tightening torque will result in damage  
on the screw.

2)  Align the center of the pipe with that of the pipe connections of the outdoor 

unit, then hand tighten the flare nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

•  Over-tightening may cause damage to the flare nut, resulting in refriger

-

ant leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the 

bare piping may result in burns or frostbite.

3-3. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3)  Using piping tape (E), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where 

the temperature and humidity are high, wind additional commercially 
sold insulation to prevent condensation.

Copper 
pipe

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Aim the copper pipe downward while removing burrs to prevent burrs 

from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on pipe having completed burr removal. (Not possible to put them on 

after flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown 

in the table. Select A mm from the table according to the tool selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flaring 

work again.

 WARNING

When installing the unit, securely 
connect the refrigerant pipes before 
starting the compressor.

 CAUTION

When there are the ports which are 
not used, make sure their nuts are 
tightened securely.

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit 

gas pipe. (The stop valves are fully closed and covered in caps in their 
initial state.)

2)  Connect gauge manifold valve and vacuum pump to service port of stop 

valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4)  Check the vacuum with gauge manifold valve, then close gauge manifold 

valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge 

manifold valve remains in the same position. Confirm that pressure gauge 

shows -0.101 MPa [Gauge] (-760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.
7) Fully open all stop valves on the gas pipe and the liquid pipe. Operating 

without fully opening lowers the performance and this causes trouble.

8)  Refer to 1-2., and charge the prescribed amount of refrigerant if needed. 

Be sure to charge slowly with liquid refrigerant. Otherwise, composition 
of the refrigerant in the system may be changed and affect performance 
of the air conditioner.

9) Tighten cap of service port to obtain the initial status.
10) Leak  test

Stop valve 
for GAS

Gauge mani-
fold valve (for 
R410A)

Compound pressure 
gauge (for R410A)

–0.101MPa  
(–760 mmHg)

Handle 
Low

Handle High

Vacuum pump
(for R410A)

Charge hose 
(for R410A)

*Close

*Open

Hexagonal 
wrench

*4 to 5 turns

Stop valve  
for LIQUID

Pressure gauge
(for R410A)

Precautions when us-
ing the control valve

When attaching the control valve 
to the service port, valve core may 
deform or loosen if excess pres-
sure is applied. This may cause 
gas leak.

Service port

Charge hose 
(for R410A)

Body

Close

Open

Control valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then tighten part A. Do not tighten 
part A or turn the body when valve 
core is in open position.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Stop valve cap
(Torque 24.4 to 
30.4 N•m, 250 to 
310 kgf•cm)

Service port cap
(Torque 10 to 12 N•m, 
100 to 120 kgf•cm)

Service port cap
(Torque 10 to 12 N•m, 
100 to 120 kgf•cm)

Stop valve cap
(Torque 21.5 to 
27.5 N•m, 220 
to 280 kgf•cm)

3.  FLARING WORK AND PIPE CONNECTION

Содержание MXZ-6E120VAD2

Страница 1: ... Air Conditioner MXZ 6E120VAD2 English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit ...

Страница 2: ...e intermediate connection Incomplete connecting and securing could cause fire n Do not install the unit in a place where inflammable gas may leak If gas leaks and accumulates in the area around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet It could cause a fire or an electric shock ...

Страница 3: ...ecommended to install a baffle board on the air outlet side of the outdoor unit Avoid the following places for installation where air conditioner trouble is liable to occur Where flammable gas could leak Where there is much machine oil Salty places such as the seaside Where sulfide gas is generated such as hot spring sewage waste water Where there is high frequency or wireless equipment Where ther...

Страница 4: ...lt M10 370 mm 417 mm When the piping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according...

Страница 5: ...e sure to fix both cable and wire with cable clamps Connecting order Connect the terminal block in following order A B C D E F P DR Terminal block for indoor outdoor unit Cable clamps 600 370 Service panel Screws Note Removing the handle increases the effectiveness of the wiring operation Be sure to reinstall the handle 2 OUTDOOR UNIT INSTALLATION Terminal block for DRED Interface DRED Interface P...

Страница 6: ...ith Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely 4 1 PURGING PROCEDURES AND LEAK TEST 1 Remove service port cap of stop valve on the side of the outdoor ...

Страница 7: ...eration mode 1 Be sure to turn off the main power for the air conditioner before making the setting 2 Set the 3 of SW1 on the outdoor controller board to ON to enable this function 3 To lock the operation mode in COOL DRY mode set the 4 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Descrip...

Страница 8: ...event electronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lit Lit Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lit Not lit Lit Completed Problem corrected or norm...

Страница 9: ...blank indd 15 2017 10 31 10 24 48 ...

Страница 10: ...blank indd 16 2017 10 31 10 24 48 ...

Страница 11: ...blank indd 17 2017 10 31 10 24 48 ...

Страница 12: ...VH79B003H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: