4-6. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units oper-

ate properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi-

nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.

Make sure that the following is done.
•  Power is supplied to the unit.
•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 
a malfunction.

Procedure
Press the piping/wiring correction switch (SW87)  minute or more after turning on the 
power supply.

•  Correction completes in 0 to 20 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW87) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW87) again.

When  the  result  was  “cannot  be  corrected”,  press  the  piping/wiring  correction  switch 

(SW871) again to cancel this function. Then, confirm the wiring and piping combination 

in a conventional manner by operating the indoor units one by one.

•  The  operation  is  done  while  the  power  is  supplied.  Make  sure  not  to  contact  parts 

other than the switch, including the P.C. board. This may cause electric shock or burn 
by hot parts and live parts around the switch. Contacting the live parts may cause P.C. 
board damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimi-

nation before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED 
(Red)

LED2 

(Yellow)

LED3 

(Green)

Lighted

Lighted

Once

Result of piping/wiring correction function

LED 
(Red)

LED2 

(Yellow)

LED3 

(Green)

Result

Lighted

Not lighted

Lighted

Completed
(Problem corrected or 
normal)

Once

Once

Once

Not completed 
(Detection failed)

Other indications

Refer to “SAFETY PRE-
CAUTIONS WHEN LED 
FLASHES” located behind 
the service panel.

5.  RELOCATION AND MAINTENANCE

5-1. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmos-
phere.
) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 

MPa [Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation on all the indoor units.
 

To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 5 seconds, connect the power 
supply plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 
minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

*  If  too  much  refrigerant  has  been  added  to  the  air  conditioner  system,  the  pressure  may  not  drop  to  0.05  MPa  [Gauge]  (approx.  0.5  kgf/cm

2

),  or  the 

protection function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to 
collect all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have 
been relocated.

6) Stop the emergency COOL operation.
 

Press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details.

When  pumping  down  the  refrigerant,  stop  the  compressor  before  disconnecting 
the refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

4-7. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air fil

-

ters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

BH79A023H0

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 00-830, JAPAN

BH79A023H01_en.indd   7

2014/01/21   11:12:01

Содержание MXZ-6D120VA

Страница 1: ...e Air Conditioner MXZ 6D120VA English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit ...

Страница 2: ...as could be generated n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or mat...

Страница 3: ...ar outdoor unit so as to reduce vibration transmitted from there 500 or more 200 or more 350 or more 100 or more 100 or more 500 or more 100 or more Service space 350 or more 350 or more When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate Whe...

Страница 4: ...The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the back both sides and top are open More than 350 mm Outdoor unit installation Air inlet Air outlet 1 6 DRAIN PIPING FOR OUTDOOR...

Страница 5: ...utdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confi...

Страница 6: ...3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section...

Страница 7: ...o lock the operation mode in COOL DRY mode set the 2 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please n...

Страница 8: ...D2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem corrected or normal Once Once Once Not completed Detection failed Other indications Refer to SAFETY PRE CAUTIONS WHEN LED FLASHES located behind the service panel 5 RELOCATION AND MAINTENANCE 5 1 PUMPING DOWN When relocating or d...

Отзывы: