background image

En-2

2. 

Front (blowing) side open

As  long  as  space  indicated 
in  the  figure  is  provided,  it 
is  allowed  to  install  the  unit 
where  obstacles  are  behind 
and  on  the  sides  of  the  unit. 
(No obstacle above the unit)

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

Port size of outdoor unit

Optional different-diameter joints (port size of outdoor unit 

 diameter of connection pipe)

MXZ-6D

Liquid / Gas

6.35 (/4) 

 9.52 (3/8) : PAC-493PI

9.52 (3/8) 

 2.7 (/2) : MAC-A454JP

9.52 (3/8) 

 5.88 (5/8) : PAC-SG76RJ

2.7 (/2) 

 9.52 (3/8) : MAC-A455JP

2.7 (/2) 

 5.88 (5/8) : MAC-A456JP

Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit.

A UNIT

6.35 (/4) / 2.7 (/2)

B - F UNIT

6.35 (/4) / 9.52 (3/8)

FREE SPACE REQUIRED AROUND OUTDOOR UNIT

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.
•  Where neighbours are not annoyed by operation sound or hot air.
•  Where rigid wall or support is available to prevent the increase of op-

eration sound or vibration.

•  Where there is no risk of combustible gas leakage.
•  When installing the unit, be sure to secure the unit legs.
•  Where it is at least 3 m away from the antenna of TV set or radio. Op-

eration of the air conditioner may interfere with radio or TV reception in 

areas where reception is weak. An amplifier may be required for the af

-

fected device.

•  Install the unit horizontally.
•  Please  install  it  in  an  area  not  affected  by  snowfall  or  blowing  snow. 

In areas with heavy snow, please install a canopy, a pedestal and/or 

some baffle boards.

Note:

It  is  advisable  to  make  a  piping  loop  near  outdoor  unit  so  as  to  reduce 
vibration transmitted from there.

500 or more

200 or more

350 or more

00 or more

00 or more

500 or more

00 or more

Service space

350 or more 

350 or more

•  When installing the unit in an area that is enclosed with walls such 

as a verandah, be sure to have enough space as shown below. 

 

In this case, the air conditioning capacity and power consumption 
might deteriorate.

•  When installing two or more units, do not install the units in front or 

behind each other.

200 or more

00 or more

350 or more

500 or more

500 or more

1. 

Obstacles above

When  there  is  no  obstacle  in  front 
and  on  the  sides  of  the  unit,  it  is  al-
lowed  to  install  the  unit  where  an 
obstacle  is  above  the  unit  only  if  the 

space shown in the figure is provided.

3. 

Obstacles in front (blowing) only

When there is an obstacle in front of 

the unit as shown in the figure, open 

space  above,  behind,  and  on  the 
sides of the unit is required.

5. 

Service space

Provide space for service and maintenance as shown in the figure.

500 or more

00 or more

(Unit: mm)

4. 

Obstacles in front, behind and on side(s)

Note: 

When operating the air conditioner in low outside temperature, be sure 
to follow the instructions described below.
•  Never install the outdoor unit in a place where its air inlet/outlet side 

may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet 

side facing the wall.

•  To  prevent  exposure  to  wind,  it  is  recommended  to  install  a  baffle 

board on the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble 
is liable to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.
•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.
•  Where there is emission of high levels of VOCs, including phthalate 

compounds,  formaldehyde,  etc.,  which  may  cause  chemical  crack-
ing.

Height of the obstacle is 200 or less

(Unit: mm (inch))

BH79A023H01_en.indd   2

2014/01/21   11:11:58

Содержание MXZ-6D120VA

Страница 1: ...e Air Conditioner MXZ 6D120VA English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit ...

Страница 2: ...as could be generated n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or mat...

Страница 3: ...ar outdoor unit so as to reduce vibration transmitted from there 500 or more 200 or more 350 or more 100 or more 100 or more 500 or more 100 or more Service space 350 or more 350 or more When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air conditioning capacity and power consumption might deteriorate Whe...

Страница 4: ...The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the back both sides and top are open More than 350 mm Outdoor unit installation Air inlet Air outlet 1 6 DRAIN PIPING FOR OUTDOOR...

Страница 5: ...utdoor unit connecting wire B from the indoor unit correctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confi...

Страница 6: ...3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section...

Страница 7: ...o lock the operation mode in COOL DRY mode set the 2 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please n...

Страница 8: ...D2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Problem corrected or normal Once Once Once Not completed Detection failed Other indications Refer to SAFETY PRE CAUTIONS WHEN LED FLASHES located behind the service panel 5 RELOCATION AND MAINTENANCE 5 1 PUMPING DOWN When relocating or d...

Отзывы: