En-6

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air conditioner 

for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat

-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 

liquid refrigerant. Adding gas refrigerant may change the composition of the refriger-

ant in the system and affect normal operation of the air conditioner. Also, charge 

the liquid refrigerant slowly, otherwise the compressor will be locked.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

Union

Stop valve

Liquid 

pipe

Indoor 

unit

Stop valve with 

service port

Gas 

pipe

Refrigerant  gas            

cylinder  

operating valve

(for R410A)

Gauge manifold 

valve (for R410A)

Charge hose 

(for R410A)

Refrigerant gas cylinder for R410A with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

* E unit is for 

5E102VA only.

Union

Union
Union

4-3. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi

-

nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.

Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 

a malfunction.

Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the 

power supply.

•  Correction completes in 10 to 20 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW871) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW871) again.

When  the  result  was  “cannot  be  corrected”,  press  the  piping/wiring  correction  switch 

(SW871) again to cancel this function. Then, confirm the wiring and piping combination in 

a conventional manner by operating the indoor units one by one.

•  The operation is done while the power is supplied. Make sure not to contact parts other 

than the switch, including the P.C. board. This may cause electric shock or burn by hot 

parts and live parts around the switch. Contacting the live parts may cause P.C. board 

damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination 

before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED1 

(Red)

LED2 

(Yellow)

LED3 

(Green)

Lighted

Lighted

Once

Result of piping/wiring correction function

LED1 

(Red)

LED2 

(Yellow)

LED3 

(Green)

Result

Lighted Not lighted Lighted

Completed

(Problem corrected or 

normal)

Once

Once

Once

Not completed 

(Detection failed)

Other indications

Refer to “SAFETY PRE

-

CAUTIONS WHEN LED 

BLINKS” located behind 

the service panel.

4-4. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

WG79A639H01_en.indd   6

3/13/2015   3:32:43 PM

Содержание MXZ-4E83VA

Страница 1: ...υ Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendø...

Страница 2: ...h EN378 1 n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and in...

Страница 3: ...is a possibility of becoming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other 100 or more 200 or more 350 or more 500 or more 500 or more Unit mm 5 Obstacles in front behind and on side s 4 Obstacles in front and behind The unit can be used by at taching an optional ou...

Страница 4: ...piping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refr...

Страница 5: ...onveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps Route the cables or wires so as not to defor...

Страница 6: ...Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe The stop valves are fully closed and covered in caps in their initial state 2 Connect gauge manifold valve and vacuum pump to servi...

Страница 7: ... function to detect and correct the combination by following the procedures below Make sure that the following is done Power is supplied to the unit Stop valves are open Note During detection the operation of the indoor unit is controlled by the outdoor unit During detection the indoor unit automatically stops operation This is not a malfunction Procedure Press the piping wiring correction switch ...

Страница 8: ...ndoor unit installation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 0 05 MPa Gauge approx 0 0 5 kgf cm2 or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrige...

Страница 9: ...Opmerking het serienummer staat op het naamplaatje van het product Nota El número de serie se encuentra en la placa que contiene el nombre del producto Nota il numero di serie si trova sulla targhetta del prodotto Σημείωση Ο σειριακός του αριθμός βρίσκεται στην πινακίδα ονόματος του προϊόντος Nota o número de série encontra se na placa que contém o nome do produto Bemærk Serienummeret står på prod...

Отзывы: