1-6. DRAIN PIPING FOR OUTDOOR UNIT

Please perform the drain piping work only when draining from one place.

1) Provide drain piping before indoor and outdoor piping connection. 

2) Connect the soft PVC hose (L) I.D.15 mm as shown in the illustration.

3) Make sure to provide drain piping with a downhill grade for easy drain flow.

Note:

Install the unit horizontally.

Do not use the drain socket (1) in the cold regions. Drain may freeze and it makes 

the fan stop. 

The outdoor unit produces condensate during the heating operation. Select the instal

-

lation place to ensure to prevent the outdoor unit and/or the grounds from being wet 

by drain water or damaged by frozen drain water.

(1) Drain socket

(L) Soft PVC hose

2-1. CONNECTING  WIRES FOR OUTDOOR UNIT

•  Be  sure  to  attach  each  screw  to  its 

correspondent terminal when securing 

the cord and/or the wire to the terminal 

block.

•  Make earth wire a little longer than oth

-

ers. (More than 35 mm)

•  For future servicing, give extra length 

to the connecting wires.

Terminal block for power supply

1) Remove the service panel.

2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire 

(B) from the indoor unit correctly on the terminal block. Be careful not 

to make mis-wiring. Fix the wire to the terminal block securely so that 

no part of its core is appeared, and no external force is conveyed to the 

connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. After 

tightening, pull the wires lightly to confirm that they do not move.

4) Perform 2) and 3) for each indoor unit.

5) Connect power supply cord (A).

6) Fix indoor/outdoor unit connecting wire (B) and power supply cord (A) 

with the cable clamps.

7) Close the service panel securely. Make sure that 3-2. PIPE CONNEC

-

TION is completed.

•  After making connections between both power supply cord (A) and indoor/

outdoor unit connecting wire (B), be sure to fix both cable and wire with 

cable clamps.

Indoor/outdoor unit connecting wire

<OUTDOOR UNIT>

35 mm

15 mm

Lead wire

Terminal block

UNIT

UNIT

Terminal block for 

power supply

<INDOOR UNIT>

POWER SUPPLY

~/N 230 V 50 Hz

Service panel

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3-1. FLARING WORK

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool  

for R410A

Clutch 

type tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35 (1/4”)

17

0 to 0.5 1.0 to 1.5

1.5 to 2.0 13.7 to 17.7 140 to 180

ø9.52 (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7 (1/2”)

26

2.0 to 2.5 49.0 to 56.4 500 to 575

ø15.88 (5/8”)

29

73.5 to 78.4 750 to 800

Tilted Uneven Burred

Good

No good

Burr Copper pipe

Spare reamer

Pipe cutter

Smooth all 

around

Even length 

all around

Inside is shin

-

ing without any 

scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Copper 

pipe

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)

2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Aim the copper pipe downward while removing burrs to prevent burrs 

from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on pipe having completed burr removal. (Not possible to put them on 

after flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown 

in the table. Select A mm from the table according to the tool selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flaring 

work again.

3.  FLARING WORK AND PIPE CONNECTION

2.  OUTDOOR UNIT INSTALLATION

BH79A129H01_en.indd   3

10/31/2014   9:57:27 AM

Содержание MXZ-2HJ40VA

Страница 1: ...s the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Kurulum Kılavuzu TESİSATÇI İÇİN Bu kılavuzda yalnızca dış ünitenin kurulumu açıklanmaktadır İç ünite kurulum işlemini yaparken iç ünite kurulum kılavuzuna bakın English is original Orijinalin çevirisi ...

Страница 2: ... leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burs...

Страница 3: ... inner diameter or hard PVC pipe VP16 for drain socket 1 1 Note 1 Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units should be installed by licensed contractor according to local code requirements More than 100 mm More than 100 mm More than 200 mm if ther...

Страница 4: ...r unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT U...

Страница 5: ... cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 200 to 300 kgf cm Gauge manifold valve for R410A Compound pressure gauge for R41...

Страница 6: ...he test run one by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so...

Страница 7: ...tuutettu EU edustaja joka on valtuutettu laatimaan teknisen eritelmän on mainittu alla Наш упълномощен представител в ЕС който е упълномощен да състави техническото досие е както следва MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Yoji SAITO Product Marketing Director Issued 9 October 2014 Tomoyuki MIWA THAILAND Manager Quality Assurance Department MIT...

Отзывы: