4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:
 

With  this  function,  once  the  operation  mode  is  locked  to  either  COOL/DRY 
mode or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

) Be  sure  to  turn  off  the  main  power  for  the  air  conditioner  before  making  the 

setting.

2) Set  the  “”  of  SW  on  the  outdoor  display  P.C.  board  to  ON  to  enable  this 

function.

3) To lock  the operation  mode  in  COOL/DRY mode,  set the “2” of SW on  the 

outdoor display P.C. board to OFF. To lock the operation in HEAT mode, set 
the same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:
 

With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 
However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Lower the operating noise

[How to lower the operating noise]

) Be sure to turn off the main power for the air conditioner before making the setting.
2) Set the “3” of SW on the outdoor display P.C. board to ON to enable this function.
3) Turn on the main power for the air conditioner.

4-5. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units oper-

ate properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

Make sure that the following is done.
•  Power is supplied to the unit.
•  Stop valves are open.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

4-6. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air fil

-

ters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

COOL/DRY

HEAT

5.  PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
) Turn off the breaker.
2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3) Fully close the stop valve on the liquid pipe side of the outdoor unit.
4) Turn on the breaker.
5) Start the emergency COOL operation on all the indoor units.
6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and 

stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.) 

* If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 MPa [Gauge] (approx. 0.5 kgf/cm

2

), or the protec-

tion function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect all 
of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. 
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 

WARNING

JG79A641H01_en.indd   5

2013/09/06   15:47:07

Содержание MXZ-2D52VA

Страница 1: ... 2D52VA English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit JG79A641H01_en indd 1 2013 09 06 15 47 04 ...

Страница 2: ... n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete...

Страница 3: ...wer supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units should be installed by licensed contractor according to local code requirements After the leak test apply insulat ing material tightly so that there is no gap When the piping is to be at tached to a wall containing metals tin plated or metal netting use ...

Страница 4: ...unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT UNI...

Страница 5: ...e system may be changed and affect performance of the air conditioner 9 Tighten cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 2...

Страница 6: ...by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 4 6 EXPLANATION TO THE USER Using the OPERATING INSTRUCTIONS explain to the user how to use the air conditioner how to us...

Страница 7: ...A4 tombo blank indd 1 12 18 2006 9 45 16 AM ...

Страница 8: ...JG79A641H01 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A641H01_en_cover indd 2 2013 08 22 13 30 01 ...

Отзывы: